Lithium Battery Replacement - E-Mon D-Mon Installation Manual

Green class kwh/demand meter with net metering capabilities
Table of Contents

Advertisement

8.0 Lithium Battery Replacement Instructions
The E-Mon D-Mon® Green Class Net Meter has a Lithium Battery Cell, which is
used to retain the contents of SRAM and the RTC during power outages. The bat-
tery has a life expectancy greater than 8 years.
Battery Specifi cations: 25 Degree Celsius
Nominal Working Voltage:
Nominal Current Capacity:
Cell Chemical:
Operating Temperature Range:
Manufacturer:
Manufacturers Part Number:
WARNING: Only replace battery with exact manufacturer and manufacturer
part number specifi ed above.
CAUTION:
The battery is not completely discharged, therefore DO
NOT short the terminals on the battery with any
conductive material.
CAUTION:
Internal Circuit Card Components are extremely sensitive
to electrostatic discharge. Be careful not to touch internal
circuitry prior to discharging any static buildup on your
person. To discharge yourself, touch a grounded metal
object such as conduit or a metal enclosure exterior.
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
The Battery Cell is mounted in a socket
on the upper right side of the Main Power
Board. Should the battery drop below 2.4
VDC in capacity, the display will illuminate
a Battery symbol on the left margin indicat-
ing a low battery condition. Additionally, the
internal unit fi rmware will set a fl ag indicat-
ing the low battery condition. When the unit
data is next downloaded, the monitoring
facility will be alerted of the low battery
condition and schedule a service call.
Use the following procedure to replace the
Lithium Battery Cell.
TestEquipmentDepot.com
3.5VDC Output
350 mAHr
Lithium-Thionyl Chloride
-40 to +95 Celsius
Eagle-Picher
LTC-3PN
Page 18

Advertisement

Table of Contents
loading

Table of Contents