Personal Protective Equipment (Ppe); Due Application; Qualified Personnel - Siemens NXAIR M Operating Instructions Manual

Air-insulated switchgear
Table of Contents

Advertisement

2.4

Personal protective equipment (PPE)

For switchgear with proven internal arc classification according to IEC 62271 Part 200, no protective
equipment is required for operating the switchgear.
To work on switchgear where covers have to be removed, personal protective equipment has to be worn
for protection against hot gases exhausting in case of internal arc.
To select the protective equipment, the national standards and specifications of the corresponding
authorities and professional associations must absolutely be observed.
The protective equipment consists of:
Protective clothing such as bib overall and long-arm jacket from NOMEX material
(see Internet: NOMEX work clothes)
Safety shoes
Gloves
Helmet and face protection
Ear protection
2.5

Due application

The air-insulated medium-voltage switchgear type NXAIR M is a type-tested and metal-clad switchgear for
indoor installation, with type of accessibility A and internal arc classification (IAC): IAC A FLR 25 kA 1 s or
IAC A FL 25 kA 1 s according to IEC 62271 Part 200.
The switchgear can be used as indoor installation according to IEC 61936 (Power Installations exceeding
AC 1 kV) and VDE 0101 in lockable electrical service locations. A lockable electrical service location is a
room or a place that is exclusively used for operating electrical equipment and which is kept under lock and
key. Access to such a room is restricted to skilled electricians.
In the basic version, the degree of protection of the enclosure of NXAIR M medium-voltage switchgear is
IP3XD according to IEC 60529.
When the switchgear is operated within the technical parameters defined in these instructions, the air-
insulated switchgear type NXAIR M is suitable for rated voltages up to U
short-time withstand current of I
The circuit-breaker to be used in a circuit-breaker panel must only be the Siemens type 3AE.
The air-insulated medium-voltage switchgear type NXAIR M is suitable for operational switching of
AC circuits in transformer substations of public power supply systems or in industrial plants.
The medium-voltage switchgear NXAIR M is available with the panel versions:
Circuit-breaker panel
Disconnecting panel
Metering panel
Bus sectionalizer
Bus coupler
Circuit-breaker panel with HV HRC fuse
2.6

Qualified personnel

Qualified personnel in accordance with these Operating Instructions are persons who are familiar with
operation and maintenance of the product and have appropriate qualifications for their work.
Furthermore, qualified personnel must have the following training and instruction or authorization:
Training and instruction or authorization to switch on, switch off, earth and identify power circuits
and equipment / systems as per the relevant safety standards
Training and instruction regarding the applicable specifications for the prevention of accidents and
the care and use of appropriate safety equipment
Training in first aid and behavior in the event of possible accidents
139-2021.9 / 07
= 25 kA.
k
NXAIR M
General instructions
= 24 kV and a maximum rated
r
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

139-2021.9

Table of Contents