Mitsubishi Electric VL-250CZPVU-L-ERT Handbook page 22

Lossnay heat recovery ventilator
Table of Contents

Advertisement

Fig. 1
+ - + -
1
2
TM200
0-10 V sensor
The unit can be operated by the DC power supply input
from external devices.
Notes
• Misconnection may cause malfunction of external
device.
• Be sure to check the polarity.
• Be sure to connect electric wires correctly.
• Terminal block has a seal attached on No. 2 terminals.
When using No. 2 terminals, remove the seal.
Fig. 3
Air conditioner
Slim-Lossnay con-
nection cable
(included)
Mr. Slim
Controller
You can control the product by Mr. Slim's remote controller.
Extend the Slim-Lossnay interlocking cable connected to Mr.
Slim PCB. Connect the cable to TM2 of the product.
When interlocked with Mr. Slim, signals from Mr. Slim oper-
ate/stop Lossnay. (The product stops regardless of the
Enable OFF button setting.)
Notes
• Be sure to check the setting of Mr. Slim in line with the
following.
• At the selection of the remote controller functions of
Mr. Slim, check that the Lossnay connectivity setting
is set to "Not supported".
• This use method limits the functions is as below.
- Other external input functions cannot be used
together.
- Interlocking commands from Mr. Slim do not operate
the Boost/Purge modes.
Lossnay
TM2
Controller
Cable
(Field supply)
Fig. 2
1 2 3 4
TM201
By-pass
Volt-free control
Volt-free contact
When the contact is ON (closed), the signal is input, when
the contact is OFF (open), the signal is stopped.
Note
• Since the circuit ensures 1 mA when the switch is
turned on, the maximum number of switches that
can be used for Volt-Free contact input is one when
the minimum load capacity is 1 mA.
Lossnay external
control input TM2
TM2
1
2
3
CN2
Mr. Slim PCB
─ 22 ─
Switch
Rating: 15 V DC, 0.1 A
Minimum applicable load: 1 mA
Sensor
Extend the cable for wiring.
Slim-Lossnay interlocking
cable (Included)

Advertisement

Table of Contents
loading

Table of Contents