Installation Of Outdoor Unit - Toyotomi UTG-09AP User Manual

Wall mounted air conditioner inverter type
Hide thumbs Also See for UTG-09AP:
Table of Contents

Advertisement

Available languages

Available languages

4. Fix the wall pipe.
5. Check if the indoor unit is installed fi rmly and closed to the wall.
indoor
wall pipe
Note:
§
Do not bend the drain hose too excessively in order to prevent blocking.

INSTALLATION OF OUTDOOR UNIT

Step one: Fix the support of outdoor unit
(select it according to the actual installation situation)
1. Select installation location according to the house structure.
2. Fix the support of outdoor unit on the selected location with expansion
screws.
Note:
§
Take suffi cient protective measures when
installing the outdoor unit.
§
Make sure the support can withstand at least
four times of the unit weight.
§
The outdoor unit should be installed at least
3 cm above the fl oor in order to install drain
joint.
§
For the unit with cooling capacity of 2300W~5000W, 6 expansion screws
are needed; for the unit with cooling capacity of 6000W ~8000W, 8
expansion screws are needed; for the unit with cooling capacity of 10000W
~16000W, 10 expansion screws are needed.
outdoor
sealing gum
88
upper hook
lower hook of wall-mounting
frame
at least 3 cm above the fl oor
GB