●Holding register
・The holding registers (readable, changeable, 2-byte data) are as follows.
Data address
Item
40001
Run/stop command
40002
Operation mode command
40003
Set temperature command
40005
Emergency stop command
40006
CPU reset command
Compressor accumulated
40007
time all reset command
40008
Capacity Control command
Initial
Range
Units
Notes
0: stop
0
0 ~ 1
-
1: run
0: cooling
0
0 ~ 1
-
1: heating
46
36=18 ℃
36 ~ 60
0.5 ℃ /count
(23 ℃ )
60=30 ℃
0 : emergency stop release
0
0 ~ 1
-
1 : emergency stop
0
0 ~ 1
-
0: NOP 1: reset
0
0 ~ 1
-
0: NOP 1: reset
0
0 ~ 10000 0.01 /count
0–100%
If data outside the range is received, the data is not accepted and an error is returned.
MODEL NAME
Air Handling Unit Interface
MODEL TYPE
AHU-KIT-SP
ISSUE
CLASSIFICATION
SPECIFICATION
MORIKAWA
DWG NO.
REV.MARK PAGE
PSZ000Z308
21.09.17