●Holding register
・The holding registers (readable, changeable, 2-byte data) are as follows.
Data address
Item
40001
Run/stop   command
40002
Operation mode command
40003
Set temperature command
40005
Emergency stop   command
40006
CPU reset command
Compressor accumulated
40007
time   all reset command
40008
Capacity Control   command
Initial
Range
Units
Notes
0: stop
0
0 ~ 1
1: run
0: cooling
0
0 ~ 1
1: heating
46
36=18 ℃
36 ~ 60
0.5 ℃ /count
(23 ℃ )
60=30 ℃
0 : emergency stop release
0
0 ~ 1
1 : emergency stop
0
0 ~ 1
0: NOP   1: reset
0
0 ~ 1
0: NOP   1: reset
0
0 ~ 10000 0.01 /count
0–100%
If data outside the range is received, the data is not accepted and an error is returned.