Mitsubishi Electric AHU-KIT-SP Manual page 22

Air handling unit interface
Table of Contents

Advertisement

●Input register
・The following table shows the input registers (read only, 2-byte data).
Data address
Item
30001
System Run/Stop display
30002
Operation mode display
30003
Set temperature display
30004
Center/Remote display
30006
Emergency stop display
30007
Return air temperature (Master)
30008
External temperature (Master)
30009
Request capacity
Initial
Range
Units
0 : Stop
0
0 ~ 65535
1 : Run
0 : Cooling
0
0 ~ 65535
1 : Heating
46(23 ℃ ) 0 ~ 65535
0.5 ℃ /count
18 ~ 30 ℃
0 : Remote
1
0 ~ 65535
1 : Center/Remote
2 : Center
0 : Emergency stop release
0
0 ~ 65535
1 : Emergency stop
0
-32768 ~ 32767
0.1 ℃ /count
-640
-32768 ~ 32767
0.1 ℃ /count
0
0 ~ 65535
1 %/count
X_all
Notes
[Data address 30003 set temperature display example]
<0.5℃/count>
18=9℃
36=18℃
50=25℃
60=30℃
[Data address 30007 return air temperature display example]
<0.1℃/count>
10=1℃
30=3℃
500=50℃
600=60℃
MODEL NAME
Air Handling Unit Interface
MODEL TYPE
AHU-KIT-SP
ISSUE
CLASSIFICATION
SPECIFICATION
MORIKAWA
DWG NO.
REV.MARK PAGE
PSZ000Z308
21.09.17
22/38

Hide quick links: