9. Rotation control

・In cascade control, rotation control is automatically enabled.
・This control averages the compressor accumulated time of all outdoor units.
・When the outdoor unit starts operating, the outdoor unit with the lowest compressor accumulated time is preferentially operated.
・When 12 hours have elapsed since the outdoor unit started operating, the outdoor unit will be switched.
*Operation switching time: 12 hours is fixed.
・This is an example of rotation control.
Rotation control example
MODEL NAME
Air Handling Unit Interface
MODEL TYPE
AHU-KIT-SP
ISSUE
CLASSIFICATION
SPECIFICATION
MORIKAWA
DWG NO.
REV.MARK PAGE
PSZ000Z308
21.09.17
18/38