Preprocessing Blocks And Fixed Signals; Control Functions; Motor Bay Control Qccbay; Apparatus Control Scilo, Gnrlcswi, Daxcbr, Daxswi - ABB RELION 630 Series Applications Manual

Motor protection and control
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS756785 G
3.3.4
3.3.5
3.3.5.1
3.3.5.2
REM630
Application Manual
Table 14:
Interface of analog inputs
Hardware module instance Hardware channel
AIM_2
AIM_2
AIM_2
AIM_2
AIM_2
AIM_2
AIM_2
AIM_2
AIM_2
AIM_2

Preprocessing blocks and fixed signals

The analog current and voltage signals coming to the IED are processed by
preprocessing blocks. There are two types of preprocessing blocks based on 20
samples per cycle and 80 samples per cycle. All function blocks functioning at 5 ms
task time need 80 samples per cycle whereas all the rest need 20 samples per cycle.
A fixed signal block providing a logical TRUE and a logical FALSE output has been
used. Outputs are connected internally to other functional blocks when needed.
Even if the AnalogInputType setting of a SMAI block is set to
"Current", the MinValFreqMeas setting is still visible. This means
that the minimum level for current amplitude is based on UBase. As
an example, if UBase is 20 kV, the minimum amplitude for current is
20000 × 10% = 2000 A.

Control functions

Motor bay control QCCBAY

Bay control is used to handle the selection of the operator place per bay. It provides
blocking functions that can be distributed to different apparatuses within the bay. Bay
control sends information about the permitted source to operate (PSTO) and blocking
conditions to other functions within the bay, for example switch control functions.

Apparatus control SCILO, GNRLCSWI, DAXCBR, DAXSWI

Apparatus control initializes and supervises proper selection and switches on primary
apparatus. Each apparatus requires interlocking function, switch control function and
apparatus functions.
Description
CH1
Line-side phase current, IL1
CH2
Line-side phase current, IL2
CH3
Line-side phase current, IL3
CH4
Neutral current, Io
CH5
Neutral-side phase current, IL1_N
CH6
Neutral-side phase current, IL2_N
CH7
Neutral-side phase current, IL3_N
CH8
Voltage U1
CH9
Voltage U2
CH10
Voltage U3
Section 3
REM630 variants
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rem630

Table of Contents