Motor protection and control
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 3
REM630 variants
60
functions are connected to a binary recorder. In case of a fault, the binary recorder is
triggered which in turn will record all the signals connected to the recorder.
Table 16:
Signals connected to the binary recorder
Channel ID
Description
Channel 1
Operate of differential protection high stage
Channel 2
Operate of differential protection low stage
Channel 3
Differential protection internally blocked
Channel 4
Start of overcurrent low stage
Channel 5
Operate of overcurrent low stage
Channel 6
Start of instantaneous overcurrent stage
Channel 7
Operate of instantaneous overcurrent stage
Channel 8
Start of negative-sequence overcurrent stage 1
Channel 9
Operate of negative-sequence overcurrent stage 1
Channel 10
Start of negative-sequence overcurrent stage 2
Channel 11
Operate of negative-sequence overcurrent stage 2
Channel 12
Thermal overload prior alarm
Channel 13
Operate thermal overload
Channel 14
Start of low stage earth-fault protection
Channel 15
Operate of low stage earth-fault protection
Channel 16
Start of high stage earth-fault protection
Channel 17
Operate of high stage earth-fault protection operate
Channel 18
Operate of phase reversal protection
Channel 19
Operate of loss of load protection
Channel 20
Start of positive-sequence overvoltage protection
Channel 21
Operate of positive-sequence overvoltage protection
Channel 22
Start of positive-sequence undervoltage protection
Channel 23
Operate of positive-sequence undervoltage protection
Channel 24
Start of negative-sequence overvoltage protection
Channel 25
Operate of negative-sequence overvoltage protection
Channel 26
Operate of motor jam protection
Channel 27
Operate signal for stalling protection
Channel 28
Operate signal for thermal stress.
Channel 29
Lock out condition for motor restart
Channel 30
Emergency start of motor
Channel 31
Motor restart inhibit due to negative-sequence overcurrent protection stage 1
Channel 32
Motor restart inhibit due to negative-sequence overcurrent protection stage 2
Channel 33
Motor restart inhibit due to thermal overload
Channel 34
Circuit breaker closed
Channel 35
Circuit breaker opened
Channel 36
Backup trip from circuit-breaker failure protection
Table continues on next page
1MRS756785 G
REM630
Application Manual