1MRS756785 G
3.3.6
3.3.6.1
REM630
Application Manual
GUID-02640926-724F-4CFA-B189-F643DA17300B V1 EN
Figure 17:
Apparatus control
Protection functions
Stabilized three-phase differential protection MPDIF
Stabilized three-phase differential protection with low stage (biased stage) and high
stage (instantaneous stage) is used for protecting motor against winding failure. Two
sets of three phase currents from the line side, 3I, and neutral side, 3I_N, are connected
to the inputs I3P and I3P_N of MPDIF. Possible uneven current transformer saturation
creates a challenge for the differential protection. MPDIF includes AC current
transformer saturation detection-based blocking which prevents unnecessary tripping
in case of magnetizing inrush currents which may be present at switching operations,
at overvoltages or during external faults. MPDIF includes also a user-selectable DC
restraint feature. The feature decreases the sensitivity of the differential protection for
a temporary time period to avoid the motor to be unnecessarily disconnected due to
high DC currents during external faults.
The operate signal from the low and high stages are used to provide a LED indication
on the LHMI. Low stage and high stage operate outputs are connected to the
Section 3
REM630 variants
49