Working Platform For Attic Installation; Suspended Furnace Installation - Payne PG95ESA Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage 4-way multipoise, 35-in. (889 mm) condensing gas furnace
Table of Contents

Advertisement

NOTE: Local codes may require a drain pan and condensate trap when a condensing furnace is installed over a finished ceiling.
NOTE: Local codes may require a drain pan and condensate trap when a condensing furnace is installed over a finished ceiling.
COMBUSTION - AIR PIPE
(SEE VENTING SECTION)
ROLLOUT PROTECTION REQUIRED
Install 12" x 22" (305x559 mm) sheet metal in front of burner compartment
area. The sheet metal MUST extend underneath the furnace casing by 1-in.
(25 mm) with the door removed. The bottom closure panel may be used for
flame roll-out protection when bottom of furnace is used for return air connection.
Fig. 25 - - Working Platform for Attic Installation
ROLLOUT PROTECTION REQUIRED
Install 12" x 22" (204 x 559 mm) sheet metal in front of and above the burner compartment area.
The sheet metal MUST extend above the furnace casing by 1-in. (25 mm with the door removed.
A 1-in. (25 mm) clearance minimum between top of furnace and combustible material is required.
The entire length of furnace must be supported when furnace is used in horizontal position to
ensure proper drainage.
NOTE: FURNACE SHOWN IS A DIRECT-VENT APPLICATION. REFER TO THE VENTING SECTION FOR
ALLOWABLE VENT CONFIGURATIONS.
Fig. 26 - - Suspended Furnace Installation
30 IN. (762 mm)
MIN. WORK AREA
2-IN.
(51 mm)
COMBUSTION-AIR PIPE
(SEE VENTING SECTION)
2-IN.
(51 mm)
25
A150580
A150581