Mitsubishi Electric FR-A862 Instruction Manual page 83

Table of Contents

Advertisement

Inverter rating
6.1
Inverter rating
• Inverter
Model FR-A862-[ ]
Applicable motor capacity (kW)
Rated capacity (kVA)

Rated current (A)

Overload current rating
Rated voltage

Regenerative braking torque
(When the converter unit (FR-
CC2) is used)
DC power supply voltage
Control power supply auxiliary input
Permissible control power supply auxiliary input
fluctuation
Protective structure (IEC 60529)
Cooling system
Approx. mass (kg)

The applicable motor capacity indicated is the maximum capacity applicable for use of the 4-pole standard motor.

The rated output capacity indicated assumes that the output voltage is 575 V.

When an operation is performed with the carrier frequency set to 3 kHz or more, and the inverter output current reaches the value indicated in
the parenthesis, the carries frequency is automatically lowered. The motor noise becomes louder accordingly.

The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.

The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about

ND rating reference value
82
SPECIFICATIONS
SLD
400
LD
355

ND (initial setting) 280
HD
220
SLD
543
LD
494
ND (initial setting) 401
HD
303
SLD
545 (463)
LD
496 (421)
ND (initial setting) 402 (341)
HD
304 (258)
110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature
SLD
of 40°C
120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature
LD
of 50°C

150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air temperature
ND (initial setting)
of 50°C
200% 60 s, 250% 3 s, 280% 0.5 s (inverse-time characteristics) at surrounding air
HD
temperature of 40°C
Three-phase 525 to 600 V

Maximum brake
10% torque/continuous
torque
618 to 933 VDC
Single phase 525 to 600 V 50 Hz/60 Hz
Frequency 5%, voltage 10%
Open type (IP00)
Forced air cooling
163
05450
06470
450
400
355
280
645
587
494
401
647 (549)
589 (500)
496 (421)
402 (341)
243
08500
630
560
450
400
847
770
661
578
850 (722)
773 (657)
663 (563)
589 (500)
243
.