Appendix 2
Item
Pr.30 Regenerative
function selection
Pr.70 Special
regenerative brake duty
Monitor function
(Pr.52, Pr.54, Pr.158,
Pr.774 to Pr.776, Pr.992,
Pr.1027 to Pr.1034)
Input terminal function
selection
(Pr.178 to Pr.189)
Pr.187 MRS terminal
function selection
Output terminal function
assignment selection
(Pr.190 to Pr.196, Pr.313
to Pr.322)
Pr.192 IPF terminal
function selection
Inrush current limit
circuit life display, Main
circuit capacitor life
display
(Pr.256, Pr.258, Pr.259)
Pr.599 X10 terminal input
selection
Pr.872 Input phase loss
protection selection
Warning, protective
functions
90
APPENDIX
Comparison with FR-A860
FR-A860
Setting ranges "0 to 2, 10, 11, 20, 21, 100 to 102,
110, 111, 120, 121"
Initial value "0"
With the parameter
Regenerative brake duty
With (Acceptable)
DC feeding operation permission (X70), DC feeding
cancel (X71)
With (Acceptable)
Initial value "24" (MRS)
Instantaneous power failure/undervoltage (IPF),
Regenerative brake pre-alarm (RBP), DC current
feeding (Y85), Main circuit capacitor life (Y87),
Inrush current limit circuit life (Y89)
With (Acceptable)
Initial value "2" (IPF)
With the parameter
Initial value "0" (NO contact specification)
With the parameter
Regenerative brake pre-alarm (RB), Instantaneous
power failure (E.IPF), Undervoltage (E.UVT), Input
phase loss (E.ILF), Brake transistor alarm detection
(E.BE), Inrush current limit circuit fault (E.IOH)
Available
FR-A862
Setting ranges "2, 10, 11, 102, 110, 111"
Initial value "10"
Without the parameter
Regenerative brake duty
Without (Unacceptable)
DC feeding operation permission (X70), DC feeding
cancel (X71)
Without (Unacceptable)
Initial value "10" (X10)
Instantaneous power failure/undervoltage (IPF),
Regenerative brake pre-alarm (RBP), DC current
feeding (Y85), Main circuit capacitor life (Y87),
Inrush current limit circuit life (Y89)
Without (Unacceptable)
Initial value "9999" (No function)
Without the parameter
Initial value "1" (NC contact specification)
Without the parameter
Regenerative brake pre-alarm (RB), Instantaneous
power failure (E.IPF), Undervoltage (E.UVT), Input
phase loss (E.ILF), Brake transistor alarm detection
(E.BE), Inrush current limit circuit fault (E.IOH)
Not available