Veris Industries E50C A Series Installation Manual page 24

Compact power and energy meter
Table of Contents

Advertisement

Installation Guide
Power Monitoring
E50B1A, E50C2A, E50C3A
Modbus Point Map (cont.)
R/W NV Format
• 166
R
NV
UInt
• 167
R
NV
UInt
• 168
R
NV
UInt
• 169
R/W NV
UInt
• 170
R/W NV
UInt
• 171
R/W NV
UInt
• 172
R/W NV
UInt
• 173
R/W NV
UInt
• 174
R/W NV
UInt
• 175
R/W NV
UInt
• 176
R/W NV
UInt
• 177
R/W NV
UInt
• 178
R/W NV
UInt
• 257/258 R
NV
Float
• 259/260 R
NV
Float
• 261/262 R
Float
• 263/264 R
Float
• 265/266 R
Float
• 267/268 R
Float
• 269/270 R
Float
• 271/272 R
Float
• 273/274 R
Float
• 275/276 R
Float
• 277/278 R
Float
• 279/280 R
Float
• 281/282 R
Float
• 283/284 R
Float
• 285/286 R
Float
• 287/288 R
Float
• 289/290 R
Float
• 291/292 R
Float
• 293/294 R
Float
• 295/296 R
Float
• 297/298 R
Float
• 299/300 R
Float
ZL0116-0A
Page 24 of 26
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Units
Scale
Range
Most Significant Byte (MSB)
Month /
See Bytes
Day
Day 1-31 (0x01-0x1F)
Year /
See Bytes
Hour 0-23 (0x00-0x17)
Hour
Minutes /
See Bytes
Seconds 0-59 (0x00-0x3B)
Seconds
Log Register Pointer 1 –
Default is 1 (Real Energy MSR)
Log Register Pointer 2 –
Default is 2 (Real Energy LSR)
Log Register Pointer 3 –
Default is 29 (Reactive Energy
MSR)
Log Register Pointer 4 –
Default is 30 (Reactive Energy
LSR)
1-42, 146,
Log Register Pointer 5 –
155-157,
Default is 37 (Real Demand)
257-336
Log Register Pointer 6 –
Default is 38 (Reactive Demand)
Log Register Pointer 7 –
Default is 39 (Apparent Demand)
Log Register Pointer 8 –
Default is 155 (Month/Day)
Log Register Pointer 9 –
Default is 156 (Year/Hour)
Log Register Pointer 10 –
Default is 157 (Minutes/Seconds)
kWh
Real Energy Consumption (clear via reset register)
kWh
Real Energy Consumption (clear via reset register)
kW
Total Instantaneous Real Power
kVAR
Total Instantaneous Reactive Power
kVA
Total Instantaneous Apparent Power
Ratio
0.0-1.0
Total Power Factor (Total KW / Total KVA)
Volt
Voltage, L-L, Average of 3 Phases
Volt
Voltage, L-N, Average of 3 Phases
Amp
Current, Average of 3 Phases
kW
Real Power, Phase A
kW
Real Power, Phase B
kW
Real Power, Phase C
Ratio
0.0-1.0
Power Factor, Phase A
Ratio
0.0-1.0
Power Factor, Phase B
Ratio
0.0-1.0
Power Factor, Phase C
Volt
Voltage, Phase A-B
Volt
Voltage, Phase B-C
Volt
Voltage, Phase A-C
Volt
Voltage, Phase A-N
Volt
Voltage, Phase B-N
Volt
Voltage, Phase C-N
Amp
Current, Instantaneous, Phase A
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Least Significant Byte (LSB)
Month 1-12 (0x01-0x0C)
Year 0-199 (0x00-0xC7)
Minutes 0-59 (0x00-0x3B)
Log Register Selection – Write the number of the 16 bit register to be logged.
To log a 32 bit value (such as accumulators and floating point values) two log
registers must be used, one each for the most and least significant register
(MSR & LSR).
Floating Point Data
Description
Date & Time of the newest entry in the log.
After a power cycle, resets to:
Day 01
Month 01
Hour 00
Year (20) 00
TM
07132