Page 1
Kessler-Ellis Products Co. Description The KEPtrol F/C is designed to measure the net flow of boiler fuel. Separate K-Factors can be entered for A and B inputs. Two SPDT relay alarm outputs are standard. A scaled pulse output is standard for interfacing with remote devices.
Page 2
SAFETY INSTRUCTIONS The following instructions must be observed. • This instrument was designed and is checked in accordance with regulations in force EN 60950 (“Safety of information technology equipment, including electrical business equipment”). A hazardous situation may occur if this instrument is not used for its intended purpose or is used incorrectly.
SECTION 1 INTRODUCTION 1-3 Principles of Operation Presets 1-1 General Description The user may assign the two preset setpoints to any of the following: "A" rate input, "B" rate The two-setpoint, electronic, controller, is a input, the net rate or the net total. The presets microprocessor-based,panel-mounted, instrument.
-3 Principles of Operation (continued) Lockout Outcard (Optional) Unauthorized front panel changes can be RS232 or RS422 serial two-way communication is prevented by entering a user selected, four digit available. Up to 15 units can be linked together code, in the "Lockout" mode. The status of the unit can be observed but "LOCK ON"...
Page 7
1-4 Specifications (continued) Memory: Control Outputs (Each of two outputs): EEPROM stores all program and count data 1. NPN Transistor Version: (Optional) for a minimum of 10 years if power is lost. Open Collector sinks maximum of 250 mA at 30 VDC when active Reset: Note:...
SECTION 2 INSTALLATION 2-1 Receipt of Equipment fields, shielding is required for maximum When the equipment is received, the outside noise immunity. One end of the shielding packing case should be checked for damage should be connected to earth ground. Relays incurred during shipment.
SECTION 3 OPERATION 2-5 Wiring Connections and Diagrams (continued) 3-1 How to Program The initial programming of the unit is accomplished by first depressing the MENU button. After pressing the MENU button once, the display will read DEV TYP. To cycle to the next control parameter option, merely press the MENU button and LOCKOUT will appear on the display.
3-2 Frequently Asked Questions About Setting Up The Unit Q. Is there any way to backspace if the wrong Q. If CLR is not pressed, numbers can still be button is hit by accident? written over the Presets or K Factors. Will these A.
3-3 Setup Procedure For The Unit (continued) SETTING PRESET B 0 Flashes. Clears out existing A K FACTOR. PRESS DISPLAY 1 2 D 0 5 6 12.056 Flashes. Sample K Factor, or enter calculated value from PRESET B notes or worksheet. PRE B Button.
Page 13
3-3 Setup Procedure For The Unit (continued) MENU ITEM 1 DEV TYP (continued) window amount of time and calculates the This menu item is used to set up the ratemeter and averaged rate. The selected "weight" is then totalizers. Please refer to the K Factor worksheets averaged in.
3-3 Setup Procedure For The Unit (continued) If you would like to: A+B adds input pulses from A and B a. lockout the unit to prevent unwanted changes together. A-B subtracts the pulses of input b. setup serial communications B from input A. This selection determines the c.
3-3 Setup Procedure For The Unit (continued) PRESS DISPLAY UNIT ## The Unit ID Number identifies the unit for 1 1 1 1 1111 Flashes. multi-drop communications. Up to 15 units Sample Lockout Code, or enter desired value from may be on one line. A unit will stay off line until notes or worksheet.
3-3 Setup Procedure For The Unit (continued) 0 Flashes. Clears out existing High Setpoint value. 6 7 5 9 D 5 6759.5 Flashes. setting, the current driver will stay at 4 mA. This Sample High Setpoint, or enter value from notes allows for offsetting the low end of the output signal.
3-3 Setup Procedure For The Unit (continued) MENU ITEM 6 RELAY From the previous page, we are setting the This menu item is for assigning the function on RELAY Menu. which the relays trip. Relays are used for controlling rate or metering batch size.
3-4 Run Mode (continued) 3-4.4 Operation. 3-4.3 Locking the Unit A typical operation proceeds as follows: The unit is shipped from the factory unlocked. To a) Preset A is accessed and changed to the lock the unit, it must be in the Run Mode. The amount desired.
A' Rate = A Rate VDC, the current draw will be 3 mA. This should A Rate K Factor be the maximum current that the KEPtrol F/C will draw. Acceptable pulse width is determined B Pulses In = B' Rate B' Rate = B Rate by the dip switch settings (See Table 4-1 below).
4-2 DC Power Inputs (Terminals 12, 14) 4-1 Digital Pulse Inputs (continued) The Unit may be powered by an external DC 4-1.1 Input 3A - STANDARD: High Impedance (Terminal 3, 4). power supply. The supply must provide 12 - 27 Has 10 K Ohm pull down resistors to ground Volts DC and at least 280 mA of current.
SECTION 5 OUTPUTS 5-2 Scaled Pulse Output The Unit has four different possible types of 5-2.1 Scaled Pulse Output outputs for controlling external devices or The scaled pulse output corresponds to NET total. monitoring the rate and totals. They are: Relay The unit gives one pulse out for each positive Outputs, Open Collector Outputs, and Optionally factored count.
SECTION 6 TROUBLE SHOOTING AND 5-3 Optional Analog Output (Terminal 10) MAINTENANCE GUIDE 5-3.1 Electrical Characteristics of Analog Output 6-1 Warning Messages Controlled by an Open Collector transistor, it gives a linear 4 to 20 (or 0 to 20) mA sink which 6-1.1 RFFFFFFF corresponds to displayed rate or total readings.
6-2 Troubleshooting (continued) 6-2.2 Problems 6-2.2 Problems Symptom: Display will not light. Symptom: Unit not totalizing. Possible Cause: No power to unit, power to unit Possible Cause #1: Incorrect programming. not to specifications. Test Procedure: Check for programming errors, Test Procedure: See Specifications Section 1-4 for review manual.
SECTION 7 CALCULATING THE K FACTORS 6-3 Removing the Case (continued) 7-1 General 6-3.1 Input Card Modification The key to accurate measurement with The Unit Follow the instructions for removing the case in is correct scaling. The electronics of the unit have Section 6-3.
7-2.1 Calculating the K Factor for Digital Pulse Inputs. Step 4. Enter the Count K Factor. (See Section Step 1. Find out what value the pulses 3-3, Menu Item 3). represent. This should be specified on your device or with its paper work. Step 5.
8-3 Parity SECTION 8 SERIAL COMMUNICATIONS Parity is a bit of information that is inserted before the stop bit and is used to help check 8-0 Outcard RS232/RS422 Serial/Strobe Interface if the transmission is correct. In the OUTCARD setup mode, select between: This section applies to units which have the a) ODD (Parity bit is logical zero if total...
8-5 RS232 Card Wiring 8-5.2 RS232 Wiring Notes This option has a subminiture D, 25 pin, female The Unit requires only three wires for RS232 connector and is wired as a DCE (Data communication: Communications Equipment) device. If it is a) Pin 7 (Signal Ground) connected to a DTE (Data Terminal Equipment) b) Pin 2 (Receive Data)
8-7.2 RS422 Wiring Notes 8-7 RS422 Card Wiring The Unit requires only four wires for RS422 This option has a subminiture D, 37 pin, female communication: connector and is wired as a DCE (Data a) Pin 22 (Receive Data +A) Communications Equipment) device.
8-9 Strobe Wiring 8-9.1 Strobe Wiring (RS232, 25 Pin Connector) the terminal will be transmitted back for The 3 data lines are hooked up to Pins 9, 10, and verification.) Once the unit is "on line", use the 11. These lines must be held high while a strobe proper serial transmit codes to request data or set of at least 25 milliseconds is given on Pin 18.
8-10.3 RS232/RS422 Serial Input Examples 8-10.2 RS232/RS422 Serial Input Codes Example A: (S) = Space Transmit from terminal Receive from DXX(S) (Device and address number followed by The Unit space) activates The Unit that had been D13(S) [Unit 13 activated] Device #13 assigned that number.
Requests are processed on a non- Series priority basis. Normally data will begin to be KEPtrol F/C transmitted from The Unit over the RS232 or RS422 serial transmit lines within 5 msec unless Operating Voltage interrupted by a keypad entry or other signal A: 110 VAC ±15% or 12 to 27 VDC...
KEPTROL F/C Set-Up Worksheet RELAYS Model # _________________________ (If applicable) Serial # _________________________ Relay Open Collector Unit # __________________________ A TOTAL A NET R COUNTER A RATE K-FACTOR A _ _ _ _ _ _ _ _ DURation of A (0.0-9.9) _ . _...