6 Specifications

6.1 Fire Detection

Detection time and distance:
40ms - for fast fire burst or explosion
o
1.5s - for 1ft
o
4s - for 1ft
o
Field of view: 90° Horizontal, 75° Vertical
Time Delay: 0-30 seconds (adjustable)
Built-in test: Automatic and Manual

6.2 Video functionality

HD Video allowing clear imaging of fire and people at 100ft. (30m) distance.
Video recording of alarm events 1 minute before and up to 3 minutes after the flame is detected.
System integration protocol: ONVIF (Open Network Video Interface Forum) Profile S

6.3 Electrical Specifications

Operating Voltage: 24 VDC nominal (18-32 VDC)
Current Consumption:
o
Standby
o
Maximum
Cable Entries: 2x conduit entries 3/4" 14NPT or M25x1.5
Wiring: 12-20AWG (2.5-0.35mm

6.4 Outputs

Relays: Volt-free contacts rated 2A at 30 VDC
o
Alarm: Normally open
o
2
Fault
: Normally open energized
2
The FAULT relay will normally be energized and the contact will be closed during normal operation of the
detector. The contact will be open at fault condition or low voltage.
For more information & Technical support: (+1) 714-671-8500 · support@fg-detection.com
2
2
(0.1m
) N-heptane pan fire at 100 ft (30m)
2
2
(0.1m
) N-heptane pan fire at 230 ft (70m)
180mA
250mA all systems in operation (including window heater)
2
)
F101V0020.05