Page 1
DEEP SEA 6110 HOW TO PERFORM A MANUAL OFF LOAD TEST 1. Turn Breaker on the Generator to OFF position 2. Press Manual Mode button on display ONCE only...
Page 2
DEEP SEA 6110 3. Check Manual Mode LED is lit 4.a. Check Display Reads Manual Mode . 4.b. PRESS GREEN Start Button for Approx 2 seconds Engine will start up and begin the OFF load test Close generator door until the 5 minute test is over 4.c.
Page 3
DEEP SEA 6110 4.e. If engine still fails to start contact Power continuity Systems 0845 055 8455 Mobile Numbers 07770 236866 / 07903227774 5.a. Run Engine for approximately 5 Minutes This is the OFF load Generator TEST 5.b. Press RED OFF ONCE Button to STOP engine 5.c.
Page 4
DEEP SEA 6110 6. Check Display Reads Auto Mode 7. When the OFF Load test in Complete Turn the Breaker on the Generator back to ON position...