On a call for heat, the thermostat will actuate, completing
the circuit to the boiler. In turn, the ignition systems
are activated and ignition will begin.
In the event of a low water condition, an automatic low
water cut-off device will interrupted power between the low
water cut-off and the burner. The burner will remain off until
the low water condition is corrected, (i.e., manually restore
boiler water or utilize a water feeder device which will auto-
matically restore water to its normal operating level).
The venting system should be inspected at the start of each
heating season. Check the vent pipe from the boiler to the
chimney for signs of deterioration by rust or sagging joints.
Repair if necessary.
Remove the vent pipe at the base of the chimney or flue
and, using a mirror, check for obstruction and verify compli-
ance to the latest revision of the NFPA 211.
The lever of the pressure relief valve (Figure #14) on the
boiler should be operated periodically to make sure that it is
functioning properly.
ELECTRONIC LOW
WATER CUT OFF
WATER
LINE
1/4" SLOT
INSPECTION
COVER
28"
LOWER FRONT
JACKET PANEL
!
Discharge will be boiling hot water and steam.

NORMAL SEQUENCE OF OPERATION

OPERATING INSTRUCTIONS

Figure #14
PRESSURE RELIEF
VALVE
TOP JACKET
HOT
ELECTRICAL
DISCONNECT
MOUNTING
(BOTH SIDES)
WARNING
IMPORTANT TO THE INSTALLER - Before putting the
boiler in operation, test the mechanical low water cut-off
device for proper operation. While burner is on, open the
blow-off valve located in the lower portion of the cut-off
body. This will drain the water quickly from the cut-off body
and break the circuit to the burner. If it does not, replace
control.
Refill boiler to its normal water line.
The pressure relief valve should open before the steam
pressure exceeds the 15 lb. reading on the gauge. If this
pressure is exceeded and the pressure relief valve leaks
steam when the boiler is operating at normal pressures, it
should be immediately replaced. Corrosion can build up
rapidly at the valve seat and prevent its functioning as a
safety device.
START-UP AND ADJUSTMENT OF OIL BURNER
(See oil burner instructions for nozzle and electrode setting)
PANEL
Instruments are the only reliable method to de-
termine proper air adjustments. An improperly
adjusted burner causes soot and high fuel bills
because of incomplete combustion of the fuel
oil. This in turn may require excessive boiler
maintenance, service costs, and in some in-
stances, house cleaning or redecorating. A
competent service mechanic should be con-
sulted to make the proper adjustments with a
BURNER
smoke tester, CO
NOTE: Bacharach or Dwyer test kits include these instruments.
SCREWS
A.
Check oil burner nozzle to make certain it is tight in
adapter. Burner mounting bolts should be tight.
B.
Check electrode setting, as they may have been jarred
13
!
WARNING
WATER WILL BE BOILING HOT.
!
CAUTION
DO NOT SET FIRE vISUALLy.
indicator, and draft gauge.