Functional Components And Safety Devices - Midea V6-i Series Manual

Commercial air conditioners
Hide thumbs Also See for V6-i Series:
Table of Contents

Advertisement

V6-i VRF 50Hz

7 Functional Components and Safety Devices

Table 2-7.1: Functional components and safety devices
Item
Compressor discharge pipe
temperature sensor
Compressor
Crankcase heater
Fan motor
Safety thermostat
High pressure switch
Low pressure switch
High pressure sensor
System
Heat exchanger temperature
sensor
Outdoor ambient temperature
sensor
30
On
Off
7-12HP V6-i VRF
50°C = 50kΩ
25W × 2
115°C
-
Off: 4.4 (±0.1) MPa / On: 3.2 (±0.1) MPa
Off: 0.05 (±0.05) MPa / On: 0.15 (±0.05) MPa
Output voltage (V) = 1.1603 × P + 0.5
(where P is the discharge pressure in MPa)
25°C = 10kΩ
25°C = 10kΩ