Functional Components And Safety Devices - Midea VC Pro Series Engineering Data

Table of Contents

Advertisement

VC Pro VRF 50/60Hz

7 Functional Components and Safety Devices

Table 2-7.1: 8-30HP functional components and safety devices
Item
Compressor top and discharge pipe
Compressor
temperature sensors
Inverter module
Inverter module temperature sensor
Fan motor
Limit temperature
Low pressure switch
High pressure sensor
System
Heat exchanger temperature sensor
Outdoor ambient temperature sensor
48
On
Off
8-30HP
90°C = 5kΩ ± 3%
90°C = 5kΩ ± 5%
115°C
-
Off: 0.05 (±0.05) MPa / On: 0.15 (±0.05) MPa
Output voltage (V) = 1.1603 × P + 0.5
(where P is the discharge pressure in MPa)
25°C = 10kΩ
25°C = 10kΩ

Hide quick links: