Midea V6-i Series Manual page 117

Commercial air conditioners
Hide thumbs Also See for V6-i Series:
Table of Contents

Advertisement

V6-i VRF 50Hz
Project name and location
DSP1
Parameters displayed on DSP2
content
0.--
Unit capacity (Hp)
1.--
Setting number of indoor units
2.--
Operating mode
3.--
Fan speed index
4.--
Total capacity of outdoor unit
5.--
Total capacity requirement of indoor units
6.--
Main heat exchanger pipe (T3) temperature (°C)
7.--
Outdoor ambient (T4) temperature (°C)
8.--
Inverter compressor discharge temperature (°C)
9.--
Invert module (TF) temperature (°C)
10.--
Refrigerant cooling pipe (TL) temperature (°C)
11.--
Compressor discharge pressure (MPa)
12.--
Discharge superheat degree (°C)
13.--
EXVA position
14.--
Actual current (A)
15.--
Inverter compressor current (A)
16.--
Actual voltage (V)
17.--
DC bus voltage (V)
18.--
Indoor heat exchanger pipe (T2/T2B) temperature (°C)
19.--
Priority mode
Number of indoor units currently in communication with outdoor
20.--
unit
21.--
Number of indoor units currently operating
22.--
Most recent error or protection code
23.--
Software version
-- --
--
Notes:
1.
Operating mode:
0: off; 2: cooling; 3: heating; 4: forced cooling.
2.
The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 11 (fastest).
3.
Priority mode:
0: heating priority; 1: cooling priority; 2: first ON priority; 3: heating only; 4: cooling only; 5: test mode 1; 6: test mode 2.
116
V6-i Series System Commissioning Report – Sheet D
System name
Remarks
Actual value = value displayed
Refer to Note 1
Refer to Note 2
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed × 0.1
Actual value = value displayed
Actual value = value displayed × 8
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Refer to Note 3
Actual value = value displayed
Actual value = value displayed
"nn" is displayed if no error or protection
events have occurred since start-up
End
Observed values
Cooling
Heating
mode
mode