7.2 Adjustment teach full state

Necessary for aqueous media. The sensitivity of the unit is optimised. Later on,
the adjustment teach full state can be repeated at any time, an adjustment teach
empty state already carried out is not affected.
A basic teach empty state must be carried out prior to the adjustment teach
full state (→ chapter 7.1 Basic teach empty state)! If it is not possible to empty
the tank, a basic teach empty state can be carried out by simulating the empty
state (e.g. adjustment when not installed, adjustment at a higher position). For
optimum function it is necessary to carry out the "modified basic teach empty
state" (→ chapter 7.3 Modified basic teach empty state) when the tank is
emptied the next time.
Fill the tank until the sensing face of the unit is
covered.
>
For NO the LED lights, for NC it goes out.
Set the unit as normally open (output closes when the
tank is full):
[OUT ON] for min. 6 s.
Press
>
While pressing the pushbutton the LED first flashes
slowly, after 6 s more quickly. After releasing the
pushbutton, the LED lights continuously.
Set the unit as normally closed (output opens when
the tank is full):
[OUT OFF] for min. 6 s.
Press
>
While pressing the pushbutton the LED first flashes
slowly, after 6 s more quickly. After releasing the
pushbutton, the LED goes out.