Connecting The Refrigerant Piping; To Connect The Refrigerant Piping To The Indoor Unit; Connecting The Electrical Wiring - Daikin FCAHG71HVEB Installation And Operation Manual

Split system air conditioners
Hide thumbs Also See for FCAHG71HVEB:
Table of Contents

Advertisement

▪ Remove the switch box cover (a).
▪ Connect the user interface (b).
▪ Connect the power supply (1~ 220-240  V 50/60  Hz) and
earth (c).
▪ Reattach the switch box cover (a).
2 Turn ON the power.
3 Start cooling operation (see
page 10).
4 Gradually pour approximately 1  l of water through the air
discharge outlet, and check for leaks.
a
Plastic watering can
b
Service drain outlet (with rubber plug). Use this outlet to
drain water from the drain pan.
c
Drain pump location
d
Drain pipe connection
e
Drain pipe
5 Turn OFF the power.
6 Disconnect the electrical wiring.
▪ Remove the switch box cover.
▪ Disconnect the power supply and earth.
▪ Disconnect the user interface.
▪ Reattach the switch box cover.
When electrical wiring is finished already
1 Start cooling operation (see
page 10).
2 Gradually pour approximately 1  l of water through the air
discharge outlet, and check for leaks (see
wiring is not finished yet" on
4.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING
FCAHG71~140HVEB
Split system air conditioners
4P535639-1B – 2019.01
b
a
c
"6.2  To perform a test run"  on
e
d
c
b
a
"6.2  To perform a test run"  on
"When electrical
page 6).
4.2.1
To connect the refrigerant piping to the
indoor unit
CAUTION
Install the refrigerating piping or components in a position
where they are unlikely to be exposed to any substance
which may corrode components containing refrigerant,
unless the components are constructed of materials that
are inherently resistant to corrosion or are suitably
protected against corrosion.
WARNING: FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly
flammable. Refer to the outdoor unit specifications for the
type of refrigerant to be used.
▪ Pipe length. Keep refrigerant piping as short as possible.
▪ Flare connections. Connect refrigerant piping to the unit using
flare connections.
▪ Insulation. Insulate the refrigerant piping on the indoor unit as
follows:
A
a
b
c
1
B
A
A
Gas piping
B
Liquid piping
a
Insulation material (field supply)
b
Cable tie (accessory)
c
Insulation pieces: Large (gas pipe), small (liquid pipe)
(accessories)
d
Flare nut (attached to the unit)
e
Refrigerant pipe connection (attached to the unit)
f
Unit
g
Sealing pads: Medium 1 (gas pipe), medium 2 (liquid pipe)
(accessories)
1
Turn up the seams of the insulation pieces.
2
Attach to the base of the unit.
3
Tighten the cable ties on the insulation pieces.
4
Wrap the sealing pad from the base of the unit to the top of
the flare nut.
NOTICE
Make sure to insulate all refrigerant piping. Any exposed
piping might cause condensation.
4.3

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least
3  mm between the contact point gaps that provide full
disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
4 Installation
B
d
b
e f
a
b
c
d
b
3
2
1
3
g
4
g
4
Installation and operation manual
e f
2
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcahg100hvebFcahg125hvebFcahg140hveb

Table of Contents