For The Installer; About The Box; Indoor Unit; To Remove The Accessories From The Indoor Unit - Daikin FCAHG71HVEB Installation And Operation Manual

Split system air conditioners
Hide thumbs Also See for FCAHG71HVEB:
Table of Contents

Advertisement

2 About the box

For the installer

2
About the box
2.1

Indoor unit

WARNING: FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly
flammable. Refer to the outdoor unit specifications for the
type of refrigerant to be used.
2.1.1
To remove the accessories from the
indoor unit
a
b
h
l
a
Paper pattern for installation (upper part of packing)
b
General safety precautions
c
Indoor unit installation and operation manual
d
Installation guide
e
Washers for hanger brackets
f
Screws (to temporarily attach the paper pattern for
installation to the indoor unit)
g
Cable ties
h
Metal clamp
i
Insulation piece (drain pipe)
j
Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe), small (electrical wiring)
k
Drain hose
l
Insulation piece: Small (liquid pipe)
m
Insulation piece: Large (gas pipe)
3

Preparation

3.1

Preparing the installation site

WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
3.1.1
Installation site requirements of the
indoor unit
INFORMATION
The sound pressure level is less than 70 dBA.
Installation and operation manual
4
c
d
e
f
i
j
k
m
CAUTION
Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation
in
environment.
▪ Spacing. Mind the following requirements:
a
A
g
A
Minimum distance to the wall (see below)
B
Minimum and maximum distance to the floor (see below)
C
≥298 mm: In case of installation with standard decoration
panel
≥340 mm: In case of installation with design panel
≥348 mm: In case of installation with fresh air intake kit
≥378 mm: In case of installation with self-cleaning
decoration panel
a
Indoor unit
b
Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)
c
Air fan
d
Static volume (example: table)
▪ A: Minimum distance to the wall. Depends on the air flow
directions towards the wall.
a
≥1500
A
a
Air outlet and corners open
b
Air outlet closed, corners open (optional blocking pad kit
required)
c
Air outlet and corners closed (optional blocking pad kit
required)
▪ B: Minimum and maximum distance to the floor:
▪ Minimum: 2.7 m to avoid accidental touching.
▪ Maximum: Depends on the air flow directions and the capacity
class. Also make sure the "Ceiling height" field setting
corresponds with the actual situation. See
settings" on
page 8.
If air flow direction...
All-round
(a)
4-way
(a)
3-way
(a)
Optional blocking kit required
a
commercial
and
light
b
c
a
≥1500
≥2000
≥4000
b
≥500
≥200
A
A
"5.1  Field
Then B
FCAHG71
FCAHG100~140
≤3.5 m
≤4.2 m
≤4.0 m
≤4.5 m
≤3.5 m
≤4.2 m
FCAHG71~140HVEB
Split system air conditioners
4P535639-1B – 2019.01
industrial
d
(mm)
c

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcahg100hvebFcahg125hvebFcahg140hveb

Table of Contents