5.1 Precautions
Before connecting cables, ensure that all DC switches on the inverter are OFF.
Otherwise, the high voltage of the inverter may result in electric shocks.
● The device damage caused by incorrect cable connections is beyond the
warranty scope.
● Only qualified technicians can perform operations about electrical connection.
● Wear proper PPE at all time when connecting cables.
5.2 Crimping an OT or DT Terminal
Requirements for the OT or DT Terminal
●
●
●
Issue 07 (2021-07-08)
5
D ANGER
WARNING
NO TE
The cable colors shown in the electrical connection diagrams provided in this chapter are
for reference only. Select cables in accordance with local cable specifications (green-and-
yellow cables are only used for protective earthing).
If a copper cable is used, use copper wiring terminals.
If a copper-clad aluminum cable is used, use copper wiring terminals.
If an aluminum alloy cable is used, use copper-aluminum transition wiring
terminals, or aluminum wiring terminals along with copper-aluminum
transition spacers.