Carrier bryant Multi-Zone 38MARBQ09 18AA3 Series Service Manual page 26

Table of Contents

Advertisement

38MAQB09~36R--3 Outdoor Units
Outdoor Fan Error F5
Error Code
Indoor Unit or Wired Control Display – F5
Malfunction decision conditions
Supposed Causes
Troubleshooting:
Troubleshooting:
Follow the "1st Steps for DLS Troubleshooting"
in the beginning of this guide, if you have an
active error, procedure below.
Shut OFF the power supply.
Rotate the Indoor fan by hand.
Does the fan rotate freely?
Ohm out reactor, remove wires first.
Reading should be close to Zero between
terminals. Also check each connection to
ground, this should be open. If not replace.
Replace fan motor
and Main PCB
Error may only displayed every 3 minutes, during this time you may
see either "normal display" or "88" on indoor unit or wired control.
No
Yes
For Instructions on how to change
Main PCB, see Table of Contents
in beginning of this guide
If after parts replacement,
F5 is still displayed, contact
your local CE Technical
Support Rep.
F5 – Outdoor Fan Problem
Dr. Smart Display (Debugger) – E7 & E71
When the indoor fan speed is too slow (300 RPM
or less) for 3 minutes or more, the unit stops and
the LED displays the Error Code for 30 seconds.
Then retries until locks out.
• Wiring mistake
• Fan motor faulty
• PCB faulty
Dr. Smart
Display
Free up, replace any broken
parts so fan spins freely
Reactor
Location