About Smart Meter and Power Limit Function
Q: How to activate output power limit function?
A: The function can be realised as follows:
1. Make sure Smart Meter connection and communication is functioning.
2. Turn on export power limit function and set the max output power to grid on App.
Note: Even if output power limit is set to 0W, there might still be a deviation of a max of 100W
exporting to grid.
Q: Why is there still power exporting to grid after I set power limit as 0W?
A: Export limit can be 0W theoretically, but there can be a measurement deviation of around
50-100W.
Q: Can I use other brand meter to take over Smart Meter in LG system or change some
settings on Smart Meter?
A: Generally, no, because the communication protocol is integrated into inverter and Smart Meter,
other brand meters cannot communicate. Also any manual setting change could cause Meter
communication failure. An exception is when using an LG Energy Solution approved meter for
VPP operations.
Q: What is the maximum current allowed to go through CT on Smart Meter?
A: The max current for CT is 120A.
Other Questions
Q: Is there a quick way to make the system work?
27
A: For the shortest way, please refer to "LGES-5048 Quick Installation Instructions" and "LGES PV
Master Instruction".
Q: What kind of load can I use to connect on back-up side?
A: Please refer to user manual on page 12.
Q: Will the warranty of the inverter still be valid if for some special conditions we cannot
100% follow the user manual instructions on the installation or operation?
A: Normally we still provide technical support to problems caused from disobeying the instruc-
tions on the user manual, however we cannot guarantee any replacements or returns. So if
there is any special conditions where you cannot 100% follow the instructions, please contact
after-sales for suggestions.

4.3 Disclaimer

The LGES-5048 inverter is transported, used and operated under environmental and electrical
conditions. Manufacturer has the right not to provide after-sales services or assistance under
following conditions:
• Inverter is damaged during transfer.
• Inverter is out of warranty year and extended warranty is not bought.
• Inverter is installed, refitted or operated in improper ways without authority from manufacturer.
• Inverter is installed or used under improper environment or technical condition mentioned in
this user manual, without authority from manufacturer.
• Installation or configuration of the inverter does not follow requirements mentioned in this user
manual.
• The inverter is installed or operated against the requirements or warnings that are mentioned in
this user manual.
• Inverter is broken or damaged by any force majeure like lightning, earthquake, fire hazard, storm
and volcanic eruption etc.
• Inverter is disassembled, changed or updated on software or hardware without authority from
manufacturer.
• Inverter is installed, used or operated against any related items in international or local policies
or regulations.
• Any non-compatible batteries, loads or other devices connected to inverter.
Note: Manufacturer will keep the right to explain all the contents in this user manual. To
ensure IP65, inverter must be sealed well, please install the inverters within one day after
unpacking, otherwise please seal all unused terminals / holes, unused terminals / holes
are not allowed to be kept open, con rm that there is no risk of water or dust entering
the terminals / holes.
Maintenance
The inverter requires periodical maintenance, details are shown below:
• Make sure inverter is totally isolated from all DC and AC power for at least 5 mins before mainte-
nance.
• Heat sink: Please use clean towel to clean up heat sink once a year.
• Torque: Please use torque wrench to tighten AC and DC wiring connection once a year.
• DC breaker: Check DC breaker regularly, active the DC breaker 10 times in a row once a year.
• Operating DC breaker will clean contacts and extend lifespan of DC breaker.
28