Haier AB12CS1ERA Service Manual page 438

Hide thumbs Also See for AB12CS1ERA:
Table of Contents

Advertisement

Super Match
Detailed information
(The common user password is required for access)
1. Proceed through main interface→Menu→other→enter the password→Details→press "Enter" to initiate.
2. 063 is the address of the wired controller inside the group; if one unit is controlled by one wired controller, the
default address is 01; the range of this value is 01 to 16; the Indoor address is the communication address of both
indoor unit and outdoor unit, ranging from 1 to 64.
3. The wired controller address equals the corresponding value of indoor unit's group address dial code plus 1.
Figure 25
Figure 26
State setting
(This function is intended for debugging by technical personnel and can be entered by high-class users only)
1. Proceed through main interface→Menu→Other→enter the high-class user password→Status set→press "Enter"
to initiate.
2. Use the upward, downward, leftward and rightward keys to adjust the cursor; the location where the cursor stays
has the circle flickering; press "Enter" key to change it to
, and the setting is completed.
indicates "selected"
and
indicates "unselected".
3. Auto recovery: if this function is on, the state before power failure will be in the memory; after restoration of power
failure, the unit will continue operating in the state as before the power failure. If this function is off, the state will not
be memorized; if the unit is energized after power failure, it is in shutdown state; after startup, the default mode is in
automatic mode as automatic air 24°C. If the auto recovery is set to be on and the sleep function is also set, in case
of accidental power failure, the unit is in shutdown state when the power supply is resumed.
4. Master/slave setting: This setting is used for master/slave control of the wired controller and the master controller
and slave controller are set separately.
436