Kobold PDA Operating Instructions Manual

Kobold PDA Operating Instructions Manual

Pressure transmitter with digital display

Advertisement

Quick Links

Operating Instructions
for
Pressure Transmitter
with Digital Display
Model: PDA
C
A
B
r
i
g
g
s
C
o
m
p
a
n
y
C
A
B
r
i
g
g
s
C
o
m
p
a
n
y
O
r
d
e
r
f
r
o
m
:
O
r
d
e
r
f
r
o
m
:
622 Mary Street; Suite 101; Warminster, PA 18974
Phone: 267-673-8117 - Fax: 267-673-8118
Sales@cabriggs.com
-
www.cabriggs.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PDA and is the answer not in the manual?

Questions and answers

Summary of Contents for Kobold PDA

  • Page 1 Operating Instructions Pressure Transmitter with Digital Display Model: PDA 622 Mary Street; Suite 101; Warminster, PA 18974 Phone: 267-673-8117 - Fax: 267-673-8118 Sales@cabriggs.com www.cabriggs.com...
  • Page 2: Table Of Contents

    8.1. Key function ..................7 9. Configuration ....................8 9.1. Value setting ..................9 9.2. Set-up mode for PDA-15 ..............10 9.3. Set-up mode for PDA-25 and PDA-35 ..........11 10. Main Menu Items..................13 10.1. Switching point ................... 13 10.2. Hysteresis ..................13 10.3.
  • Page 3: Note

    PDA • Operating Instructions 4. Operating Principle KOBOLD pressure indicator/transmitter series PDA, are cost effective electronic pressure indicator/transmitters with digital indication of actual pressure. An analogue output (0)4 - 20 mA is available for remote transmission of the measured value. The device is optionally available in addition with a switching output.
  • Page 4: Regulation Use

    ∅ 21,3 -0,2 G 1/4 A G 1/2 A G 1/2 A * min. * min. * min. R 16 13 16 19 24 R 16 R 16 +0,2 ∅ 7 +0,2 ∅ 7 ∅ 7 +0,2 page 4 PDA 01/06...
  • Page 5: Electrical Connection

    • Mating plugs with different cable lengths are available as options. Important! The instrument electronics may be damaged if the cable connections are connected incorrectly. 7.1. Connector pin assignment PDA-15... PDA-15 Not connected +Vs/+ Supply 0 V / GND...
  • Page 6: Connector Pin Assignment Pda-25, Pda-35

    7.2. Connector pin assignment PDA-25, PDA-35… PDA-25... PDA-35... PNP-Output NPN-Output +24 V +24 V 0 V / GND 0 V / GND 0(4)-20 mA 0(4)-20 mA 0 V / GND 0 V / GND Plug Plug with cable ZUB-KAB-12K002 Connection example PDA-...P3M...
  • Page 7: Commissioning

    Normal mode (measuring mode) : Press for 3 Sec. set-up mode : Display Low/High current value Set-up mode Any time: : Next level 3 sec. : Change value or 20 sec. Without pressing any Normal Mode PDA 01/06 page 7...
  • Page 8: Configuration

    0 to upper range value End current (E-C) span 0 to upper range value upper range value 0 / 4 mA Start current selection (SCS) 1/2/4/8/16/32/64 Filter (Filt) adjusted Start adjustment (S-A,) tare 000 - 999 Change Code (CCo,) page 8 PDA 01/06...
  • Page 9: Value Setting

    End current, "E-C"). The standard sequence for changing parameters is given in the flowchart below. [from the main menu item] Set 1st position Set 2nd position Set 3rd position Adjust decimal point Save selected value or re-enter Save [to the next main menu item] PDA 01/06 page 9...
  • Page 10: Set-Up Mode For Pda-15

    9.2. Set-up mode for PDA-15 3 sec Code input Value setting Start current 7sec Value setting Store Start current End current 7sec Value setting Store End current 0-20 Start current Selection 7sec 4-20 Filter 7 levels Value setting Start adjustment...
  • Page 11: Set-Up Mode For Pda-25 And Pda-35

    9.3. Set-up mode for PDA-25 and PDA-35 3 sec Codeeingabe Setting parameter Switch Point Hysteresis Duo-Point Setting parameter On-Delay Setting parameter Off-Delay Setting parameter Contact type N.O. contact N.C. contact Save PDA 01/06 page 11...
  • Page 12 Start current 7sec Setting parameter current 7sec Setting parameter 0-20 Start current range 7sec 4-20 Filter 7 levels Set-up Startpoint 7sec Setting parameter Change code Setting parameter page 12 PDA 01/06...
  • Page 13: Main Menu Items

    This parameter setting is similar to the switch point setting. The window point is needed for processes, during which the pressure must be monitored within or outside a certain range. PDA 01/06 page 13...
  • Page 14: Switching Characteristic

    LED signals the switching status of the pressure switch. Display bar (°C) LED on Switching point Hysteresis Time / t Display bar (°C) LED on Hysteresis Duo point LED on Switching point Hysteresis Time / t page 14 PDA 01/06...
  • Page 15: Time Response

    "SCS" Start current selection (0-20 mA or 4-20 mA). The indicated value at which 0(4) mA is transmitted is entered in menu item Start current. The indicated value at which 20 mA is transmitted is entered in the menu item End current. PDA 01/06 page 15...
  • Page 16: Filter

    000, the operator must enter the set code “Cod” before entering the set-up mode. 11. Maintenance The instrument requires no maintenance when properly used. Deposits, due to fouled media, can give rise to invalid measured values. page 16 PDA 01/06...
  • Page 17: Technical Information

    N/O / N/C, duo programmable Output indicator: 1 LED ON/OFF-switch. delay: 0,5...99,5 s (separately adjustable) Response time: 0.5 s ±0.5 % f. s., (±1 % of full scale for Accuracy: spans ≤ 1,6 bar) Protection: IP 65 PDA 01/06 page 17...
  • Page 18: Order Codes

    13. Order Codes Example: PDA-15 3 R2 C315 Electrical Model/Output Connection Measuring range Connection C315=-1...0 bar B025= 0...1 bar B035= 0...1,6 bar B045= 0...2,5 bar B055= 0...4 bar PDA-15=Standard 0(4)-20 mA B065= 0...6 bar R2=G ¼ PDA-25=0(4)-20 mA, B075= 0...10 bar R4=G ½...
  • Page 19: Dimensions

    14. Dimensions Info! The matching M12x1 box with 2 m cable for the M12x1 plug connector is available under order code ZUB-KAB-12K002. (Fig. with box) PDA 01/06 page 19...