SECTION 4 - VAV UNITS
OUTDOOR AIR TEMPERATURE RESET -
COOLING
Field Wiring
For Unoccupied cooling operation connect zone sen-
sor wiring to CTB1 terminals 13 and 14 located inside
the control panel (see Appendix 1).
Miscellaneous Connections
All units provided with a VFD include a factory mount-
ed static pressure sensor (SPS1). The unit can also
have an optional second static pressure sensor, (SPS2).
The second static pressure transducer would be used
if the main supply duct split into two main branches.
The control can be programmed to maintain the low-
est input, highest input or the average of the two. The
sensor is factory wired and requires field installation
of 1/4" ID sensor tubing to the selected duct location.
A field supplied static pressure probe and tubing must
be installed in the field prior to unit start-up.
Refer to the unit IOM Form 145.05-NOM3 for details
on how to install the static pressure probe and tubing.
Programming
Options Key -Unit Data Subsection
• UNIT TYPE = VARIABLE AIR VOLUM.
• UNIT SIZE = Select Unit Size in tons from the
listed choices.
• REFRIGERANT TYPE = Select R22, 407C, or
R410A.
• COMP STAGING SEQ = For units with four
stages of cooling select SIMPLE, for units with
six stages of cooling select MIXED (on four com-
pressor units only).
Options Key - Supply System Subsection
• HIGH DUCT STATIC SW = Should be set to
INSTALLED if the optional High Duct Static
Switch is installed.
• SF VFD BYPASS = Should be set to INSTALLED
if the optional SF VFD Bypass is installed.
• DUCT PRESS SENSOR 2 = Should be set to IN-
STALLED if an optional 2
is installed.
12
duct static transducer
nd
Setpoints Key - Cooling Subsection
• SAT LOW SETPOINT = 50.0 °F - 60.0 °F.
• SAT HIGH SETPOINT = 55.0 °F - 70.0 °F.
• UNOCC ZONE COOLING SETPOINT = 60.0
°F - 95.0 °F.
• RAT COOLING SETPOINT = RAT HEATING
SETPOINT + 2 °F TO RAT SETPOINT FOR
HIGH SAT.
• OAT SETPOINT FOR LOW SAT = OAT
SETPOINT FOR HIGH SAT + 5.0 °F TO 90.0 °F.
• OAT SETPOINT FOR HIGH SAT = 60.0 °F TO
OAT SETPOINT FOR LOW SAT - 5.0 °F.
Setpoints Key - Supply System Subsection
• DUCT STATIC RESET LOW SETP = 0 INWG
- Span.
• DUCT STATIC RESET HIGH SETP = 0 INWG
- Span.
• DUCT STATIC OVER PRESSURE = 0 INWG
- Span.
• DUCT STATIC TRANSDUCER SPAN = 1.25,
2.5, 5.0 INWG.
Program Key - Cooling Subsection
• SAT RESET METHOD = OUTSIDE AIR.
Program Key - Supply System Subsection
• SF VFD BYPASS MODE = Place in VFD BY-
PASSED to place the unit in SF VFD Bypass
Mode.
• DUCT PRESS CNTRL = HIGH, LOW, AVER-
AGE, DUCT PRESSURE 1 ONLY.
Date / Time Key
Enter Correct Date and Time.
FORM 145.05-SU3 (611)
ISSUE DATE 6/01/2011