Locating and Mounting Condensing Unit

Locating Condensing Unit.
Condensing Unit must be located and
installed where there is an unrestricted
area.
Avoid
areas
corrosive vapors or flammable materials.
Avoid locating units too close to walls.
Fan intake and discharge air space should
be at least 1m and 2m from wall. Other
sides should be at least 0.5m from wall.
Mounting Condensing Unit.
Mounting base should be concrete or
steel sufficient to support between 2 to 5
times the weight of condensing unit.
Condensing units must be mounted using
pads to avoid vibration or shifting.
The anchor bolts should be used to fix
Spring Mounted Compressor.
Semi-hermetic compressor unit use the mounting assembly shown in Figure 11, the
shipping spacer is to be in place during shipment to insure maximum support for the
compressor body during transit.
Before the unit is put in operation, the shipping spacer should be removed and discarded.
Before operating the unit, it is necessary to follow these steps.
1. Remove the upper nuts and washers.
2. Remove and discard the shipping spacers.
3. Install the rubber spacer. (rubber spacer tied to compressor.)
4. Replace the upper mounting nuts and washers.
5. Allow 1/16" between the upper nut and the rubber spacer as Figure 11.
where
there
are
No impediments should be located in
front of condensing units intake and
discharge.
If above is not followed correctly noise
and inadequate air flow may result.
Condensing units should be located away
from general public and the street.
Make sure units are kept horizontal.
the unit and tightened with spring washer
and nuts.