A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpm/ft
low GPM requirements.
Features
1. Very low water flow requirements.
2. Cover plate attachment (Plain or Perforated)
with ½" (13mm) Total adjustment.
3. Thread-On/Thread-Off or Push-On/Thread
Off cover attachment option.
4. Smooth aesthetic ceiling profile.
5. Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen-
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ
from standard sprinklers primarily in their response time
and water distribution patterns.
Model RFC30, RFC43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de-
flector. Residential distribution patterns are higher and
generally contain a finer droplet size than standard sprin-
kler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has
demonstrated, in fire testing, an ability for controlling
residential fires, and thereby providing significant evacu-
ation time for occupants.
The RFC30, RFC43 and RFC49 Sprinklers provide the
best form of fire protection by combining an attractive ap-
pearance and ½" (13mm) of cover adjustment for ease
of installation. The small diameter cover plate is easily
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model RFC30 (SIN RA0611)
Model RFC43 (SIN RA0612)
Model RFC49 (SIN RA0616)
Residential Flat Concealed
Sprinklers
2
with
and positively attached and blends into the ceiling, con-
cealing the most dependable fire protection available, an
automatic sprinkler system.
The RFC30, RFC43 and RFC49 are UL Listed Residen-
tial Sprinklers to be installed in the residential portions
of any occupancy in accordance with NFPA 13, 13R, &
13D.
The RFC30, RFC43 and RFC49 can reduce the need
for precise cutting of drop nipples. The threaded cover
plate assembly can be adjusted without tools to fit ac-
curately against the ceiling. The fire protection system
need not be shut down to adjust or remove the cover
plate assembly.
Bulletin 006
Plain Cover Plate
Perforated Cover Plate
I
Rev.

Advertisement

loading
Need help?

Need help?

Do you have a question about the RFC30 and is the answer not in the manual?

Questions and answers

Summary of Contents for Reliable RFC30

  • Page 1 ½” (13mm) of cover adjustment for ease need not be shut down to adjust or remove the cover of installation. The small diameter cover plate is easily plate assembly. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523...
  • Page 2 Application and Installation The RFC30, RFC43 and RFC49, for residential instal- When inserting or removing the wrench from the sprin- lations, use a 165°F (74°C) fusible solder link in a tun- kler/cup assembly, care should be taken to prevent dam- ing fork style sprinkler frame with a drop-down deflector.
  • Page 3 Standard cover finish: [Chrome] [White] [Specialty – specify]. Residential concealed Concealed Sprinkler Specifi cation sprinklers shall be Reliable Model RFC30, SIN RA0611 Sprinklers shall be cULus Listed low flow residential con- (Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006) cealed sprinklers with drop-down deflector and adjust- or Model RFC49, SIN RA0616 (Bulletin 006).
  • Page 4 Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

This manual is also suitable for:

Rfc43Rfc49Ra0611Ra0612Ra0616