Reliable JL-17 Quick Start Manual

Early suppression fast response sprinkler

Advertisement

Quick Links

Features:
1. cULus, VdS, and LPCB listed as a nominal
K16.8 (240 metric) ESFR sprinkler.
2. FM Approved as a quick-response, storage
and non-storage, sprinkler.
3. Fusible link operating element.
4. Compact design allows piping to be in-
stalled farther from the ceiling and obstruc-
tions compared with larger sprinklers.
Listings and Approvals
1. Listed by Underwriters Laboratories Inc. and UL certified
for Canada (cULus) - Category Code VNWH.
2. FM Approved as a quick-response, storage and non-
storage, sprinkler.
3. VdS Schadenverhütung GmbH (VdS).
4. Loss Prevention Certification Board (LPCB).
5. CNBOP Technical Approval.
Product Description
The Reliable Model JL-17 Early Suppression Fast
Response (ESFR) Sprinkler with a nominal k-factor of
16.8 (240 metric). This sprinkler is designed to respond
quickly to growing fires and will deliver a heavy water
discharge to "suppress" rather than "control" fires. FM
Global classifies the Model JL-17 as a quick-response
sprinkler, storage and non-storage, when the sprinkler is
used in accordance with FM Global Property Loss Pre-
vention Data Sheets.
The Model JL-17 ESFR sprinkler utilizes a levered fus-
ible alloy solder link in either a 165°F (74°C) or a 212°F
(100°C) rating. Model JL-17 sprinklers are cULus Listed
for compliance with UL/ULC 1767, including the high
clearance test for rack storage.
The Model JL-17 ESFR sprinkler was designed to be
shorter and more compact than other ESFR sprinklers.
The shorter sprinkler allows piping to be installed farther
from the ceiling and obstructions. The JL-17 ESFR sprin-
kler is also less susceptible to damage due to smaller
deflector and frame design. The lighter JL-17 ESFR
passed rough use and abuse listing tests without plastic
protectors.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model JL-17 (SIN RA1914)
K16.8 (240 metric)
Early Suppression
Fast Response Sprinkler
Model JL-17 ESFR Sprinkler
Application and Installation
The Model JL-17 ESFR sprinkler is intended for instal-
lation in accordance with NFPA 13 and FM Loss Pre-
vention Data Sheets 2-0 and 8-9, as well as the require-
ments of any Authorities Having Jurisdiction. See Table
1 for information on NFPA and FM Global design criteria
for the Model JL-17 sprinkler.
Use only the Model J1 sprinkler wrench for removal
and installation. Any other type of wrench may damage
the sprinkler. A grooved wrench boss is provided on
the sprinkler to limit the potential for the wrench to slip
during installation.
Model J1
Sprinkler Wrench
Sprinklers not tightened to recommended torque may
cause leakage or impairment of the sprinkler. Damage
sprinklers must be replaced immediately.
Bulletin 019
H
Rev.
When handling sprin-
klers,
hold
sprinklers
only on frame arms and
do not apply any force on
the link assembly. Sprin-
klers should be tight-
ened between 14 - 40 ft-
lbs (19 - 54 N-m) torque.

Advertisement

loading
Need help?

Need help?

Do you have a question about the JL-17 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Reliable JL-17

  • Page 1 The lighter JL-17 ESFR cause leakage or impairment of the sprinkler. Damage passed rough use and abuse listing tests without plastic sprinklers must be replaced immediately. protectors. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523...
  • Page 2 4 - 13 in (100 - 330mm) for non- smooth ceilings per FM Data Sheet 2-0. Maintenance The Model JL-17 ESFR Sprinkler should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinkler with soap and water, ammonia or any other cleaning fluid.
  • Page 3 Storage Type NFPA Open Frame (that is, no solid shelves) Refer to NFPA 13, Refer to FM 2-0 Single, Double, Multiple-Row, or Portable Rack Storage Chapters 16 and 17. and FM 8-9. of Class I-IV and Group A or B Plastics Solid Pile or Palletized Storage of Class I-IV Refer to NFPA 13, Refer to FM 2-8...
  • Page 4 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years. Manufactured by Reliable Automatic Sprinkler Co., Inc.

This manual is also suitable for:

Ra1914Sin ra1914