Figure 6:
Diagnostic and system events are always available for transfer whichever protocol is in use
and cannot be configured.
The IEC 60870-5-103 section only appears when the protocol is configured.
3.3.2

Logical node GGIO (Generic process I/O) configuration

Signals, which are not mapped to the IEC 61850 Model by the HMI500 tool automatically, can
only be transferred to SCS/SMS indirectly. They have to be assigned to binary I/Os first.
The binary I/Os are represented by the logical node GGIO in the 61850 model. By default, no
signals are mapped to the GGIO logical node.
The mapping configuration is opened by selecting the CR channel and pressing button CR
event config, OC channel and OC event config for binary inputs, respectively.
Distributed busbar protection REB500
Communication protocol manual IEC 61850
Configuring signals as events
© 2019 - 2020 Hitachi Power Grids. All rights reserved
Section 3
Interbay bus functions
13000024-IEC18000608-1-en.vsdx
GUID-49BCE444-5FF8-4226-800B-E1399532950B v3