Configuring Iec 61850-8-1 Ibb; Station Protection Specific Signals - ABB RELION REB500 Communication Protocol Manual

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Section 3
Interbay bus functions
IEC18000607 V1 EN-US
Figure 5:
Table 3:
Setting
Time zone correction
(h/m)
Daylight saving time
SNTP
UTC
SNTP1
SNTP2
3.3
Configuring IEC 61850-8–1 IBB
3.3.1

Station protection specific signals

For IEC 61850, all important station protection specific signals are mapped automatically to
the 61850 Model (see
be changed manually. This is shown by an inactive tick check box for IBB 1 or IBB 2,
respectively.
The logical Node and the name of the data attribute of a mapped signal are shown in the IEC
61850-8-1 box. The IEC 61850-8-1 box is not shown for signals which are not transferred to the
SCS/SMS.
10
Dialog box for configuring time synchronization
Configuration of IEC 61850-8-1 time synchronization
Description
Time zone setting (hours/minutes)
Dialog for switching from standard time to
summertime and vice versa
SNTP must be used as time source if 61850 is
used
UTC must be selected if 61850 is used
TCP/IP Address of the SNTP time master
TCP/IP Address of the SNTP standby time
master
Section
4.3.1). This is done by the HMI500 tool automatically and cannot
© 2019 - 2020 Hitachi Power Grids. All rights reserved
13000023-IEC18000607-1-en.vsdx
Default setting
See Screenshot
See Screenshot
None
No
127.0.0.1
127.0.0.1
GUID-39D6617C-7870-4A9B-A05F-E7DA895A61CD v3
Distributed busbar protection REB500
Communication protocol manual IEC 61850
1MRK 511 450-UEN Rev. C