9.
PRODUCT MODELS AND MAIN SPECIFICATIONS
9-1 Models and Main Specifications.
Model
Power supply
Refrigerant
Evaporating temperature
Operating
condition
Outdoor temperature
Outer dimensions (H×W×D) (mm)
Product mass
Connecting
Liquid pipe
refrigerant
Gas pipe
piping
Sound pressure level (dB(A)) (*1)
High-pressure side
Design
pressure
Low-pressure side
Note:
*1. The figures for the outside unit models show values measured at a distance of 1 m in the front and a height of 1.5 m.
Front side
Values measured with the models actually installed are usually larger than the values shown as a result of ambient noise and reflections.
*2. When the connected piping length is shorter than 50 m, piping size can be decreased piping size to one grade.
*3. Values are subject to change without notice for product improvements.
*4. When the outdoor temperature is low, the temperature reading may be below the target evaporating temperature set for the protection of the unit.
Operation manual
5
LREQ5
1,680 ×
635 × 765
166 kg
Ø9.5
Ø22.2
55 dB
(bar)
38
(MPa)
3.8
(bar)
25
(MPa)
2.5
1 m
LREQ6
LREQ8
3 phase 50 Hz 380~415 V
–45°C~+10°C
–20°C~+43°C
1,680 ×
1,680 ×
635 × 765
930 × 765
930 × 765
166 kg
242 kg
Ø9.5
Ø12.7 (*2)
Ø12.7 (*2)
Ø22.2
Ø28.6
56 dB
57 dB
38
38
3.8
3.8
25
25
2.5
2.5
LREQ10
LREQ12
LREQ15
R410A
1,680 ×
1,680 ×
1,680 ×
930 × 765
1,240 × 765
242 kg
242 kg
331 kg
Ø12.7
Ø28.6
Ø28.6
59 dB
61 dB
38
38
3.8
3.8
25
25
2.5
2.5
Air cooled refrigeration condensing unit
LREQ20
1,680 ×
1,240 × 765
337 kg
Ø12.7
Ø12.7
Ø34.9
Ø34.9
62 dB
63 dB
38
38
3.8
3.8
25
25
2.5
2.5
LREQ5~20B7Y1
4PW74303-1C – 2016.02