Connecting

6.4 Plugging in terminal blocks

6.4
Plugging in terminal blocks
Hazardous Voltage.
Can Cause Death, Serious Injury, or Property Damage.
Before starting work, therefore, disconnect the system and devices from the power supply.
Requirement
You must have removed the terminal blocks, for the purpose of replacing a device, for example.
Procedure when plugging in the terminal blocks
Note
Removable terminal blocks are mechanically coded to prevent polarity reversal
The removable terminal blocks are mechanically coded to prevent polarity reversal and are
labeled with A, B, C or D on the inside. Only use the slots shown in the diagram below.
Note
Plug-in sequence
Connect terminal block B before terminal block A, and D before C.
Step
Operating instruction
1
Insert the removable terminal block into the
mechanically coded guiderail of the device
2
Slide the removable terminal block back until it
audibly engages.
3
Check that the clip of the removable terminal
block closes flush with the front panel
46
WARNING
.
.
1
2
Equipment Manual, 05/2020, NEB926246402000/RS-AE/007
Figure
B
A
3TK2810-1 safety-related speed monitor
D
C