Pressure Monitoring
Bluetooth® Differential Pressure / Air Velocity Transducer
Product Overview
PX3
The PX3 transducer can measure either air pressure or velocity with the flip of a switch.
Patent Pending
The PX3 is available in three installation configurations: duct, panel or universal. Duct and
50
panel models have two pressure and velocity options: 0-1 in. WC / 0-3,000 ft/min or
1-10 in. WC / 3,000-6,000 ft/min with four field-selectable sub-ranges. The universal
NOTICE
model comes in one pressure/velocity range: 0-10 in. WC / 0-7,000 ft/min with seven
• This product is not intended for life or
safety applications.
field-selectable sub-ranges for pressure and eight for velocity. All variants are available
• Do not install this product in hazardous
with and without display. The PX3 has an IP65/NEMA 4 environmental rating and a 5-year
or classi ed locations.
limited warranty.
• Read and understand the instructions
before installing this product.
• Turn o all power supplying equipment
The Veris Sensors App provides the ability to connect to a device and configure a variety
before working on it.
of field-selectable parameters remotely from a smartphone via Bluetooth wireless
• The installer is responsible for
technology. The app allows users to create and store commonly used parameters that
conformance to all applicable codes.
will reduce commissioning time and provide assurance that all parameters are properly
If this product is used in a manner not speci ed
configured with no call backs. The app can also create a trend log while connected,
by the manufacturer, the protection provided
by the product may be impaired. No
providing critical data for troubleshooting purposes. iOS® users can download the app
responsibility is assumed by the manufacturer
through the
iOS App Store
for any consequences arising out of the use of
this material.
through the
Google Play™
see the
Veris Sensors App User's Guide
This device complies with part 15 of the FCC
on the Veris website.
Rules. Operation is subject to the following
two conditions: (1) This device may not cause
harmful interference, and (2) this device must
Product Identification
accept any interference received, including in-
terference that may cause undesired operation.
Enclosure
PX3
Changes or modifications not expressly ap-
proved by the party responsible for compliance
D = Duct
could void the user's authority to operate the
P = Panel
equipment.
*8-point calibration
This device complies with Industry Canada
license-exempt RSS standard(s). Operation is
Local Display
subject to the following two conditions: (1) this
device may not cause interference, and (2) this
PX3U
device must accept any interference, including
L = LCD Display
interference that may cause undesired opera-
X = No Display
tion of the device.
*16-point calibration
Cet appareil est conforme aux normes d' e x-
emption de licence RSS d'Industry Canada. Son
fonctionnement est soumis aux deux conditions
suivantes : (1) cet appareil ne doit pas causer
d'interférence et (2) cet appareil doit accepter
toute interférence, notamment les interférenc-
es qui peuvent affecter son fonctionnement.
Z207504-0M
Page 1 of 8
©2021 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
Installation Guide
Pressure Monitoring
Specifications (cont.)
Zero Drift (1-year) 1 in. WC (250 Pa) models: 2.5% FS typ.; 10 in. WC (2,500 Pa) models: 0.25% FS typ.
Zero Adjust Pushbutton auto-zero and digital input (2-pos terminal block)
Operating Environment -20 to 60 °C (-4 to 140 °F)***
Altitude of Operation 0 to 3000 m
Pollution Degree 2
Humidity Range 100% RH, non-condensing
Mounting Location For indoor or outdoor use (display will not function below 0 °C (32 °F))
Fittings Brass barb; 0.24" (6.1 mm) o.d.
Suggested Cable Shielded:
Belden #9939 (22 AWG) 3-wire multi-conductor (or similar)
Belden #9940 (22 AWG) 4-wire multi-conductor (or similar)
Belden #9939 (22 AWG) 5-wire multi-conductor (or similar)
Unshielded:
Belden #8443 (22 AWG) 3-wire multi-conductor (or similar)
Belden #8444 (22 AWG) 4-wire multi-conductor (or similar)
Belden #8445 (22 AWG) 5-wire multi-conductor (or similar)
Bluetooth Frequency
2.402 to 2.480 GHz (Bluetooth version 4.2), enabled by DIP switch, enabled by DIP switch
Range
Maximum Output Power 0 dBm
Limited Warranty 5 years
Environmental Rating IP65, NEMA 4
Flammability Rating UL 94 5VA fire retardant ABS, plenum rated
EMC Conformance: EN 61000-6-3 and A1, Class B, EN 61000-6-1, EN61326-1 and EN61326-2-3.
* Class 2/II power source.
** For measured values between 200 and 7000 ft/min (1 and 35 m/s).
*** Display will not function below 0 °C (32 °F).
Installation, Wiring
1. Plan the installation. Panel or duct mount?
& Configuration
Static Pressure
Panel Installations
Duct Installations
Velocity with VFXP Probe
For velocity applications, use the VFXP Series air velocity/measurement probe or AA18,
AA19 or AA20 velocity pitot tubes. For use with the PX3P (panel) and PX3U (universal)
models in Velocity mode only. Sold separately.
Z207504-0M
Page 3 of 8
©2021 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
PX3 Series
on their smart device. Android users can download the app
store. For instructions on downloading and operating the app,
and
Veris Sensors App Quick Start Guide
Local Display
NIST Certificate*
Range
L = LCD Display
N = NIST
01 = Pressure: 0 to 1 in. WC / 0 to 250 Pa
X = No Display
X = None
Velocity: 0 to 3,000 ft/min / 0 to 15 m/s
02 = Pressure: 0 to 10 in. WC/0 to 2,500 Pa
Velocity: 0 to 6,000 ft/min / 0 to 30 m/s
NIST Certificate*
Range
N = NIST*
05 = Pressure: 0 to 10 in. WC / 0 to 2500 Pa
X = None
Velocity: 0 to 7000 ft/min / 0 to 35 m/s
Differential Pressure
FILTER
Velocity with AA18/AA19/AA20 Pitot Tube
Installation Guide
Pressure Monitoring
Dimensions
in. (mm)
1.6
(42)
3.5
(88)
3.1
(78)
4.4
(112)
Specifications
Media Compatibility Dry air or inert gas
Input Power Three-wire Volt mode: 24 Vac or 12-30 Vdc*
Output Power Field-selectable: 2-wire, loop-powered 4-20 mA
01 Pressure
Pressure
Range
Mode
available
Velocity
Mode
02 Pressure
Pressure
Range
Mode
Velocity
Mode
05 Pressure
Pressure
Range
Mode
Velocity
Mode
Response Time Standard: T95 in 20 sec, Fast: T95 in 2 sec, DIP switch selectable
Mode Unidirectional or bidirectional, DIP switch selectable
Display (Option) Pressure mode: Signed 3-1/2 digit LCD, indicates pressure, overrange indicator
Proof Pressure 3 psid (20, 600 Pa)
Burst Pressure 5 psid (34, 500 Pa)
Pressure Mode Accuracy ±1% FS (combined linearity and hysteresis)
Velocity Mode Accuracy ±90 ft/min (±0.45 m/s) plus 5% of measured value**
Temperature Effect 1 in. WC (250 Pa) models: 0.05%/°C; 10 in. WC (2,500 Pa) models: 0.01%/°C
0621
Z207504-0M
Page 2 of 8
©2021 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
Installation Guide
Pressure Monitoring
Installation, Wiring
& Configuration
(cont.)
0621
Z207504-0M
Page 4 of 8
©2021 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
1.6
(42)
3.5
(88)
7.4
(188)
Two-wire mA mode: 12-30 Vdc*
Minimum input voltage for 4 to 20 mA operation: 250 Ω loop = 12 Vdc; 500 Ω loop = 19 Vdc
(DC only, clipped and capped), 24 Vac/dc or 3-wire 0-5V/0-10V
Minimum load resistance for Volt operation: 5 kΩ
Unidirectional: 0.1/0.25/0.5/1.0 in. WC, switch selectable
Bidirectional: ±0.1/±0.25/±0.5/±1.0 in. WC, switch selectable
Unidirectional: 25 Pa/50 Pa/100 Pa/250 Pa, switch selectable
Bidirectional: ±25 Pa/±50 Pa/±100 Pa/±250 Pa, switch selectable
500/1,000/2,000/3,000 ft/min
2.5/5/10/15 m/s
Unidirectional: 1.0/2.5/5/10 in. WC, switch selectable
Bidirectional: ±1.0/±2.5/±5/±10 in. WC, switch selectable
Unidirectional: 250/500/1,000/2,500 Pa, switch selectable
Bidirectional: ±250/±500/±1,000/±2,500 Pa, switch selectable
3,000/4,000/5,000/6,000 ft/min
15/20/25/30/35 m/s
Unidirectional: 0.1/0.25/0.5/1/2.5/5/10 in. WC, switch selectable
Bidirectional: ±0.1/±0.25/±0.5/±1/±2.5/±5/±10 in. WC, switch selectable
Unidirectional: 25/50/100/250/500/1,000/2,500 Pa, switch selectable
Bidirectional: ±25/±50/±100/±250/±500/±1,000/±2,500 Pa, switch selectable
500/1000/2000/3000/4000/5000/6000/7000 ft/min
2.5/5/10/15/20/25/30/35 m/s
Velocity mode: Signed 4-1/2 digit LCD, indicates velocity, overrange indicator
(Relative to 25 °C) 0 to 50 °C (32 to 122 °F)
2. For duct mount applications, thread the probe into the back of the device housing, as
shown in the dimensional drawing.
3. Configure the internal tubing for the selected installation method as described below.
Duct mount tubing configuration:
a. Connect the right-side tube to the rear brass barb marked as "-" on the
underside of the device housing.
b. Connect the left-side tube to the probe in the back of the device housing.
Panel mount tubing configuration:
a. Connect the right-side tube to the rear brass barb marked as "-" on the
underside of the device housing.
b. Connect the left-side tube to the front brass barb marked as "+" on the
underside of the device housing.
Tubing for Duct Mount
Tubing for Duct Mount
4. Mount the transducer (see the screw hole diagram below).
in. (mm)
2.3
(59)
CTR-CTR
3.3
(83)
CTR-CTR
To Pickup Tube
0.3
(7)
0621
Tubing for Panel Mount
Tubing for Panel Mount
2.5
(62)
To Pickup
Tube
3.2
(81)
0.5
(13)
1.4
(35)
0621

Advertisement

loading

Summary of Contents for Veris PX3 Series

  • Page 1 0621 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C.
  • Page 2 0621 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C.