Veris T-VER-H970-200 Connection Instructions

Dc current transducer for use with hobo h22, u12, u30, and ux120-006m data loggers and hobo data nodes

Advertisement

Quick Links

Veris DC Current Transducer (CT) Connection Instructions
®
For use with HOBO
H22, U12, U30, and UX120-006M data loggers and HOBO data nodes
Applies to this Veris CT:
Onset Part No.
Current Range
T-VER-H970-200
0-200 Amps DC
Installing CT in an energized electrical enclosure or on any energized conductor can result in severe injury or death. This CT is for
installation by qualified personnel only. To avoid electrical shock, do not perform any installation or servicing of this CT unless you
are qualified to do so. Disconnect and lock-out all power sources during installation and servicing. Please read transducer user's
manual for instructions and use.
This document provides instructions on connecting the Veris CT listed above to each of the
following:
FlexSmart
Analog Module used with HOBO H22 series data loggers
Analog Sensor Port used with HOBO U30 series data loggers
4-20mA cable or voltage adapter used with the U12 and UX120-006M data loggers and
ZW series data nodes
It also lists configuration values used by HOBOware
Required:
Veris CT listed above
HOBO H22, U12, U30, or UX120-006M data logger, or HOBO ZW data node
FlexSmart Analog Module, Onset Part No: S-FS-CVIA (for H22 series); Analog Sensor Port option (for U30 series);
4-20mA cable, Onset Part No. CABLE-4-20mA or voltage adapter, Onset Part No. CABLE-ADAP5 (for U12,
UX120-006M, or ZW series)
HOBOware Pro Software, version 2.2.1 or higher (2.4.0 or higher for U30 series; 3.0 or higher for ZW series; 3.6 or
higher for UX120-006M)
Customer-supplied lengths of hook-up wire
Connecting the CT to the Analog Module or Port:
*
The applicable output terminal f rom the CT is shown connected to the channel 2 input terminal (S2+) on the FlexSmart Analog Module.
© 2007–2013 Onset Computer Corporation. All rights reserved. Onset, HOBO, and HOBOware are registered trademarks and FlexSmart is a trademark of Onset
Computer Corporation. Other products and brand names may be trademarks or registered trademarks of their respective owners.
11464-G MAN-VERIS-CT
Distributed by MicroDAQ.com, Ltd.
Output
4-20mA (or 0-5VDC) representing 0 to 50/100/200 Amps DC
DANGER!
®
Pro software to configure the logger for CT.
H22 Connection
HOBO H22 Series Data Logger
S-FS-CVIA
FlexSmart Analog Module
DC Current Transducer
FlexSmart Analog Module
for 4-20mA Output*
If available, the channel 1 input terminal (S1+) can be used instead.
—HIGH VOLTAGE HAZARD
DC Current Transducer
All wiring
DC
customer-supplied
LOAD
FlexSmart Analog Module
for 0-5VDC Output*
www.MicroDAQ.com
Veris Part No.
H970HCA
Veris DC Current
Transducer
DC Current Transducer
(603) 746-5524

Advertisement

loading

Summary of Contents for Veris T-VER-H970-200

  • Page 1 Disconnect and lock-out all power sources during installation and servicing. Please read transducer user’s manual for instructions and use. This document provides instructions on connecting the Veris CT listed above to each of the following: ™...
  • Page 2 Veris DC Current Transducer (CT) Connection Instructions U30 Connection HOBO U30 Series Data Logger Analog Sensor Port DC Current Transducer LOAD All wiring customer-supplied Analog Sensor Port DC Current Transducer Analog Sensor Port DC Current Transducer for 4-20mA Output* for 0-5VDC Output* The applicable output terminal f rom the CT is shown connected to the channel 2 input terminal (Ch2 Signal) on the Analog Sensor Port.
  • Page 3 Veris DC Current Transducer (CT) Connection Instructions Configuring the Data Logger for the CT, using HOBOware Pro Software: HOBOware Pro software provides a configuration file for the CT. The table below lists the recommended configuration values that this file contains. For information on loading configuration files, refer to the software documentation.

This manual is also suitable for:

H970hca