Special conditions for safe use

Lids securing fasteners shall be property class A4 with a yield stress of
344N/mm
Units may be painted or fitted with optional accessories, some of which
are made of non-metallic material or have a non-metallic coating which
could potentially generate an ignition-capable level of electrostatic
charge under certain extreme conditions (such as high pressure steam)
which might cause a build-up of electrostatic charges on the non-
conducting surfaces. Additionally, cleaning of the equipment should
only be done with a damp cloth.
Under rated conditions, the cable entries reach a temperature exceeding
158 °F (70 °C), and the branching point exceeds a temperature of 176 °F
(80 °C); this shall be considered when installing cable glands, and only
cables that have temperature ratings suitable for the application shall be
used.
Flameproof joints are not intended to be repaired.
The Rosemount 975 Series Flame Detectors can be fitted with an
unmolded (non-encapsulated) end of line (EOL) resistor. Such a resistor
can only be fitted into the flameproof "Ex d" compartment as indicated in
the instructions. The EOL resistor shall be rated at 1.56 kΩ, 1 W
minimum.
To reduce the risk of ignition of a flammable or explosive atmosphere,
strictly adhere to the following statements:
WARNING
Do not open when energized.
Do not open when an explosive atmosphere is present.
Temperature at branching point may exceed 212 °F (100 °C).
CAUTION
Potential electrostatic charging hazard
See instructions.