INSTALLATION AND
MAINTENANCE INSTRUCTIONS
IDP-Relay-6
Six Relay Control Module
SPECIFICATIONS
Normal Operating Voltage: 15-32 VDC Stand-By
Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Maximum IDC
Wiring Resistance:
Accessories:
Wire Gauge:
Relay Current:
BEFORE INSTALLING
If the modules will be installed in an existing operational
system, inform the operator and local authority that the
system will be temporarily out of service. Disconnect the
power to the control panel before installing the modules.
This system contains static sensitive components. Always
CURRENT RATING
3 A
2 A
.9 A
.9 A
.5 A
1 A
.3 A
1.5 A
.7 A
2 A
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed)
state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communi-
cate with the panel before connecting circuits controlled by the module.
K200-15-00
1.45 mA
32 mA (assumes all six relays
have been switched once and
all six LEDs solid on)
32°F to 120°F (0°C to 49°C)
10 to 85% Non-condensing
6.8˝ H × 5.8˝ W × 1.0˝ D
40 ohms
IDP-ACB cabinet and chassis
12-18 AWG
30 mA/Relay Pulse (15.6
mS pulse duration) pulse
under panel control
MAXIMUM VOLTAGE
30 VDC
30 VDC
110 VDC
125 VDC
30 VDC
30 VDC
125 VAC
25 VAC
70.7 VAC
25 VAC
ground yourself with a proper wrist strap before handling
any circuits so that static charges are removed from the
body. The housing cabinet should be metallic and suit-
ably grounded.
NOTICE: This manual should be left with the owner/
user of this equipment.
GENERAL DESCRIPTION
The IDP-Relay-6 Six Relay Control Module is intended
for use in an intelligent alarm system. Each module is
intended for Form-C switching applications, which do
not require wiring supervision for the load circuit. A
single isolated set of dry relay contacts is provided for
each module, which is capable of being wired for either
normally open or normally closed for each operation.
Each module has its own address. A pair of rotary code
switches is used to set the address of the first module
from 01 to 94. The remaining modules are automatically
assigned to the next five higher addresses. Provisions are
included for disabling a maximum of three unused mod-
ules to release the addresses to be used elsewhere. Each
IDP-Relay-6 module also has panel controlled green LED
indicators. The panel can cause the LEDs to blink, latch
on, or latch off.
Contents include:
(6) 1 × 3 Terminal Blocks
(1) 1 × 4 Terminal Blocks
1
(2) 1
/
˝ (32mm) Stand offs
4
(4) Machine Screws
(2) Nuts
(1) Shunt (NOTE: For the disable position, not more
than one shunt shall be installed at the same time)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected
to a compatible Silent Knight system control panel.
LOAD DESCRIPTION
Resistive
Resistive
Resistive
Resistive
Inductive (L/R=5ms)
Inductive (L/R=2ms)
Inductive (PF=.35)
Inductive (PF = .35)
Inductive (PF=.35)
Inductive (PF=.35)
WARNING
1
APPLICATION
Non-coded
Coded
Non-coded
Non-coded
Coded
Coded
Non-coded
Non-coded
Non-coded
Non-coded