FireLock
®
Specific Application Back-To-Back Attic Protection Scheme,
Quick Response Upright, K5.6 (8.0), K8.0 (11.5)
FL-SA/DS, V5621
1.0 PRODUCT DESCRIPTION
SIN
ORIENTATION
K-FACTOR1
CONNECTION
MAX. WORKING PRESSURE
GLOBE RE-DESIGNATION
AVAILABLE WRENCHES
SPRINKLER
Upright
Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar
Min. Operating Pressure: UL: 7 psi/48 kPa/.5 bar
Temperature Rating: See tables in section 2.0
1
For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0.
2.0 CERTIFICATION/LISTINGS
Sprinkler Model
SIN
BB46
V8122
BB46/GAP
V8122/V5623
BB79
V8123
BB79/GAP
V8123/V5623
BB1012
V8124
BB1012/GAP
V8124/V5623
GAP
V5623
DS
V5621
NOTES
Listings and approval as of printing.
Listed to be utilized per NFPA 13 in conformance with the New Technology and Equivalency Sections.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
46.03 16398 Rev B Updated 04/2021
Series FL-SA/GAP and FL-SA/BB
FL-SA/GAP, V5623
SPECIFIC APPLICATION ATTIC SPRINKLERS
V5621
UPRIGHT
UPRIGHT
5.6 Imp./8.1 S.I.
5.6 Imp./8.1 S.I.
1/2" NPT/15mm BSPT
1/2" NPT/15mm BSPT
175 psi (1200 kPa)
175 psi (1200 kPa)
GL5621
GL5623
V56 Open End
V81 Open End
Nominal K Factor
Temperature Ratings
Imperial
8.0
cULus 200°F/93°C
8.0/5.6
cULus 200°F/93°C
8.0
cULus 200°F/93°C
8.0/5.6
cULus 200°F/93°C
8.0
cULus 200°F/93°C
8.0/5.6
cULus 200°F/93°C
5.6
cULus 200°F/93°C
5.6
cULus 200°F/93°C
© 2021 Victaulic Company. All rights reserved.
FL-SA/BB, V8122
V5623
V8122
UPRIGHT
8.0 Imp./11.5 S.I.
3/4" NPT/ 20mm BSPT
175 psi (1200 kPa)
GL8122
Listing Agency/
Approved
Area of Use
RIDGE/GABLE
RIDGE/GABLE and
GAP at EAVE
RIDGE/GABLE
RIDGE/GABLE and
GAP at EAVE
RIDGE/GABLE
RIDGE/GABLE and
GAP at EAVE
EAVE/HIP
HIP/SINGLE SLOPE
1
FL-SA/BB, V8123
FL-SA/BB, V8124
V8123
UPRIGHT
8.0 Imp./11.5 S.I.
3/4" NPT/ 20mm BSPT
175 psi (1200 kPa)
GL8123
Maximum
Roof Span
ft
60
84
60
84
60
84
N/A
N/A
46.03
V8124
UPRIGHT
8.0 Imp./11.5 S.I.
3/4" NPT/ 20mm BSPT
175 psi (1200 kPa)
GL8124
Roof Pitch
4:12 to less than 7:12
4:12 to less than 7:12
7:12 to less than 10:12
7:12 to less than 10:12
10:12 to 12:12
10:12 to 12:12
SEE LAYOUT CRITERIA
SEE LAYOUT CRITERIA

Advertisement

loading
Need help?

Need help?

Do you have a question about the FireLock Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Victaulic FireLock Series

  • Page 1 Listed to be utilized per NFPA 13 in conformance with the New Technology and Equivalency Sections. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. victaulic.com 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved.
  • Page 2 Lodgement Spring: Stainless steel Installation Wrench: Ductile iron Sprinkler Frame Finishes: Plain brass NOTE • For cabinets and other accessories refer to separate sheet. 4.0 DIMENSIONS FL-SA/GAP FL-SA/DS FL-SA/BB 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 3 MAX 84 ft 10:12 to 12:12 V5623 EAVE/HIP SEE LAYOUT CRITERIA V5621 HIP/SINGLE SLOPE SEE LAYOUT CRITERIA FIGURE 4A FIGURE 4B FIGURE 4: SPAN MEASUREMENT/SPRINKLER SPACING LOCATIONS 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 4 PARALLEL WITH DIRECTION OF THROW OF FL-SA/BB SPRINKLERS • See Figure 9 and Figure 10 for detailed layout criteria. FIGURE 5B FIGURE 5: PROTECTION OPTIONS FL-SA/BB FL-SA/GAP 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 5 (depending on sprinkler placement). • See Figure 11A and Figure 11C for detailed sprinkler layout criteria. FIGURE 6: SINGLE SLOPE PROTECTION OPTIONS = Model Gap = Model DS 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 6 Model FL-SA/DS in accordance with Figure 13 or Model FL-SA/GAP in accordance with Figure 14 may be utilized. FIGURE 7: UNDER-HIP PROTECTION OPTIONS FL-SA/GAP FL-SA/DS 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 7 HIP area. • See Figure 16 for detailed layout criteria. FIGURE 8: ADJACENT HIP PROTECTION OPTIONS FL-SA/GAP FL-SA/DS 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 8: Installation

    Attic sprinklers have not been evaluated for use with spray foam insulation. FIGURE 9: GABLE LAYOUT CRITERIA MODEL FL-SA/BB 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 9 The metal wire netting is intended to hold the insulation in place should the insulation become wetted by the operation of the sprinkler. Attic sprinklers have not been evaluated for use with spray foam insulation. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 10 FIGURE 11B: 1 ROW DS SPRINKLER (HIP SHOWN AT CORNER) FIGURE 11C: 2 ROW DS SPRINKLER (HIP SHOWN AT CORNER) FIGURE 11: SINGLE SLOPE SPACING CRITERIA 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 11 The metal wire netting is intended to hold the insulation in place should the insulation become wetted by the operation of the sprinkler. Attic sprinklers have not been evaluated for use with spray foam insulation. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 12 Attic sprinklers have not been evaluated for use with spray foam insulation. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 13 Attic sprinklers have not been evaluated for use with spray foam insulation. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 14 Attic sprinklers have not been evaluated for use with spray foam insulation. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 15 Attic sprinklers have not been evaluated for use with spray foam insulation. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 16 The metal wire netting is intended to hold the insulation in place should the insulation become wetted by the operation of the sprinkler. Attic sprinklers have not been evaluated for use with spray foam insulation. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 17: Hydraulic Design

    >40 ft to ≤60 ft 10:12 to 12:12 22.6 BB1012 V8124 ≤40 ft 10:12 to 12:12 V5623 SEE LAYOUT CRITERIA 12.8 V5621 SEE LAYOUT CRITERIA 12.8 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 18 The metal wire netting is intended to hold the insulation in place should the insulation become wetted by the operation of the sprinkler. Attic sprinklers have not been evaluated for use with spray foam insulation. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 19 • Example shown in FIGURE 20B results in 12 sprinklers to be calculated. (18 x 0.75 = 12) FIGURE 20A FIGURE 20B FIGURE 20: HYDRAULIC CALCULATIONS REQUIRED FOR HIP – WET SYSTEM (HIP TRUSS/JACK TRUSS CONSTRUCTION) FL-SA/GAP FL-SA/DS 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 20 FIGURE 21: HYDRAULIC CALCULATIONS REQUIRED FOR HIP – DRY SYSTEM (HIP TRUSS/JACK TRUSS CONSTRUCTION) (Examples shown in these figures are for reference only. Actual sprinklers selected based on piping configuration which results in the most demanding hydraulic demand.) 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 21 • Calculate all sprinklers within the hip area shown shaded. See Figure 23. • Minimum sprinkler flow is 20 gpm per sprinkler. FL-SA/GAP FL-SA/DS FIGURE 23: HYDRAULIC CALCULATIONS REQUIRED FOR DS @ HIP (FRAMING MEMBERS PARALLEL TO SLOPE) 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 22 1 ROW PROTECTION CALCULATION FIGURE 24B FFIGURE 24C 2 ROW PROTECTION CALCULATION #1 2 ROW PROTECTION CALCULATION #2 FIGURE 24: HYDRAULIC CALCULATIONS REQUIRED FOR WET SYSTEM SINGLE SLOPE DESIGN 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 23 1 ROW PROTECTION CALCULATION FIGURE 25B FFIGURE 25C 2 ROW PROTECTION CALCULATION #1 2 ROW PROTECTION CALCULATION #2 FIGURE 25: HYDRAULIC CALCULATIONS REQUIRED FOR DRY SYSTEM SINGLE SLOPE DESIGN 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 24 2 ROW PROTECTION CALCULATION #1 FIGURE 26C FFIGURE 26D 2 ROW PROTECTION CALCULATION #2 2 ROW PROTECTION CALCULATION #3 FIGURE 26: SINGLE SLOPE WITH HIP – WET SYSTEM DESIGN 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 25 1 ROW PROTECTION CALCULATION FIGURE 27B FFIGURE 27C 2 ROW PROTECTION CALCULATION #1 2 ROW PROTECTION CALCULATION #2 FIGURE 27: SINGLE SLOPE WITH HIP – DRY SYSTEM DESIGN 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 26 These obstructions can have an impact on the upper portion of the spray pattern from sprinklers. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 27 FIGURE 30: SUSPENDED HORIZONTAL OBSTRUCTIONS GL-SS/ BB, RE AND DS SPRINKLERS FL-SA/BB FL-SA/BB FL-SA/GAP FIGURE 31A FIGURE 31E FIGURE 31: FL-SA/BB AND FL-SA/DS SPRINKLER OBSTRUCTIONS (CONT. NEXT PAGE) 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 28 FIGURE 34: DEFLECTOR LESS THAN 12" ABOVE STIFFENERS (NO OBSTRUCTION) BB spray pattern. See Figure 32. “FL-SA/BB” FIGURE 32: DEFLECTOR COMPLETELY BELOW STIFFENERS AND HORIZONTAL WEB MEMBERS (NO OBSTRUCTION) 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 29 FL-SA/BB sprinkler (i.e. sprinkler frame arms are perpendicular to the roof trusses). See Figure 28. FIGURE 35: SPRINKLER FRAME ORIENTATION TO ROOF SLOPE 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 30 Refer to Figure 36B. Insulation is for fire protection purposes. It is not freeze protection. CPVC must be installed in accordance with the CPVC Manufacturer's installation guide instructions. 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 31 FIGURE 37D: ANGLED SPRIG FIGURE 37E: ARM OVER SPRIG FIGURE 37F: VERTICAL SPRIG WITH SWING JOINT FIGURE 37: CPVC ALLOWANCE GUIDELINES WET SYSTEMS ONLY (GABLE/DOWNSLOPE AREA) 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...
  • Page 32 FIGURE 38: EXPOSED CPVC AT HIP ROOF AREAS FIGURE 39: EXPOSED CPVC AT HIP ROOF AREAS (HORIZONTAL BRANCHLINE OVER JOISTS) (HORIZONTAL BRANCHLINE WITHIN JOISTS) WET SYSTEMS ONLY WET SYSTEMS ONLY 46.03 16398 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com...