Victaulic
FireLock
®
Specific Application Back-To-Back Attic Protection Scheme,
Quick Response Upright, K5.6 (8.0), K8.0 (11.5)
FL-SA/DS, V5621
1.0 PRODUCT DESCRIPTION
SIN
ORIENTATION
K-FACTOR1
CONNECTION
MAX. WORKING PRESSURE
GLOBE RE-DESIGNATION
AVAILABLE WRENCHES
SPRINKLER
Upright
Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar
Min. Operating Pressure: UL: 7 psi/48 kPa/.5 bar
Temperature Rating: See tables in section 2.0
1
For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0.
2.0 CERTIFICATION/LISTINGS
Sprinkler Model
SIN
BB46
V8122
BB46/GAP
V8122/V5623
BB79
V8123
BB79/GAP
V8123/V5623
BB1012
V8124
BB1012/GAP
V8124/V5623
GAP
V5623
DS
V5621
NOTES
•
Listings and approval as of printing.
•
Listed to be utilized per NFPA 13 in conformance with the New Technology and Equivalency Sections.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
46.03 16398 Rev B Updated 04/2021
Series FL-SA/GAP and FL-SA/BB
™
FL-SA/GAP, V5623
SPECIFIC APPLICATION ATTIC SPRINKLERS
V5621
UPRIGHT
UPRIGHT
5.6 Imp./8.1 S.I.
5.6 Imp./8.1 S.I.
1/2" NPT/15mm BSPT
1/2" NPT/15mm BSPT
175 psi (1200 kPa)
175 psi (1200 kPa)
GL5621
GL5623
V56 Open End
V81 Open End
■
Nominal K Factor
Temperature Ratings
Imperial
8.0
cULus 200°F/93°C
8.0/5.6
cULus 200°F/93°C
8.0
cULus 200°F/93°C
8.0/5.6
cULus 200°F/93°C
8.0
cULus 200°F/93°C
8.0/5.6
cULus 200°F/93°C
5.6
cULus 200°F/93°C
5.6
cULus 200°F/93°C
© 2021 Victaulic Company. All rights reserved.
FL-SA/BB, V8122
V5623
V8122
UPRIGHT
8.0 Imp./11.5 S.I.
3/4" NPT/ 20mm BSPT
175 psi (1200 kPa)
GL8122
■
Listing Agency/
Approved
Area of Use
RIDGE/GABLE
RIDGE/GABLE and
GAP at EAVE
RIDGE/GABLE
RIDGE/GABLE and
GAP at EAVE
RIDGE/GABLE
RIDGE/GABLE and
GAP at EAVE
EAVE/HIP
HIP/SINGLE SLOPE
1
FL-SA/BB, V8123
FL-SA/BB, V8124
V8123
UPRIGHT
8.0 Imp./11.5 S.I.
3/4" NPT/ 20mm BSPT
175 psi (1200 kPa)
GL8123
Maximum
Roof Span
ft
60
84
60
84
60
84
N/A
N/A
46.03
V8124
UPRIGHT
8.0 Imp./11.5 S.I.
3/4" NPT/ 20mm BSPT
175 psi (1200 kPa)
GL8124
Roof Pitch
4:12 to less than 7:12
4:12 to less than 7:12
7:12 to less than 10:12
7:12 to less than 10:12
10:12 to 12:12
10:12 to 12:12
SEE LAYOUT CRITERIA
SEE LAYOUT CRITERIA