Part C: Connecting 501/RCG Entry to Body
STEP C1: Remove any end caps
Transit caps should be pulled o the products by hand.
Metallic energised end caps must be uninstalled by reversing the steps described in Part D (Entries) and Part E (Bodies).
IMPORTANT: System must be de-energised before any metallic end caps are removed.
STEP C2: Engage entry and body
Ensure that the metallic outer components of the body portion can rotate freely around the cable. If needed further loosen the middlenut
and backnut. Ensure that the keyways are aligned and hand engage the body into the entry.
STEP C3: Tighten Centrenut (6)
Hand tighten the centrenut (6) into the entry (2). Use a wrench to ensure the entry (2) cannot turn. Use a second wrench to
tighten the centrenut (6) until it is wrench tight.
2
Grip here with wrench
STEP C4: Tighten Middlenut (11)
Hand tighten the middlenut (11) to the centrenut (6). Use a wrench to ensure the centrenut (6) cannot turn. Use a second
wrench to apply a further 1/4 turn to the middlenut.
STEP C5: Install backnut (12)
Tighten the backnut (12) by hand until a seal is formed around the cable. Use a wrench/spanner to grip the middlenut (11). While preventing
the middlenut (11) turning, use a second wrench to apply one further full turn to the backnut (12). Use the middlenut guide as an indication
that the backnut is in the correct position to suit cable diameter. A diameter scale below is provided to assist in this process.
AI 2045 - Issue B / Page 6 of 9
50
50
Male Keyway
Female Keyway
6
Grip here with wrench
11
Grip here with wrench
55
60
60
11
6
12
65
70
70
Body is free to spin around cable
Product supplied may di er from that shown.
80
Diameter Scale (mm)
75
80
Correct when printed A4 Booklet Styl
Images for illustration purposes only.
e

Advertisement

loading