STEP A5: Fit crimped conductors into entry
Using the insertion tool supplied with the product, push the pin contact into the entry (2) until it clicks
into place. Repeat for all contacts. Inspect contacts to ensure they are straight - if needed adjust with the
insertion tool.
NOTE: The ground contact sits higher than the signal positions as it is designed to mate rst/break last.
STEP A6: Complete wiring of conductors
Installation of the 501/RCG Entry to the equipment is now complete. Proceed to terminate the conductors inside the equipment as
required.
Once installation is complete, the 501/RCG Entry may be terminated in one of the following ways:
-Fit transit cap for environmental protection
- Fit Entry Energised End Cap which may allow product to be energised (See Part D)
- Mate Entry with 501/RCG Body (See Part C)
Part B: Terminating 501/RCG Body
STEP B1: Prepare Cable
Slide backnut (12), middlenut (11) and armour clamp ring (10) onto cable.
Con rm orientation of armour clamp ring is correct (see table below).
Cut cable length, strip outer sheath and cut armour. Use lengths as shown in table below.
Strip Lengths
Seal/Ring Size
Dim
Os-A
x
20mm
25mm
y
50mm min
Tape Armour
After tape is spread, ensure ends are
trimmed at 90° as shown
AI 2045 - Issue B / Page 3 of 9
*Click*
2
y
B
x
x
10
11
12
Armour Clamp Ring Orientation
Orientation
Gland
Size
Equipment Side
Os-A
0.8 - 1.25mm
B
1.25 - 1.6mm
Images for illustration purposes only.
Product supplied may di er from that shown.
Equipment Side
0 - 0.8mm
0 - 0.7mm