value is displayed when the inlet is closing. The letters "StP" are displayed
if the inlet is not moving.
If the inlet opening is displayed as a percentage, the REMAINING RUN
TIME / OPENING menu shows the current opening (in %) of the air inlet.

Resetting the Inlet Position

Resetting the actuator's position allows clearing all accumulated time off-
sets caused by the frequent openings and closings of the inlet. It is highly
suggested to reset inlet positions frequently to make sure they are always
accurate.
Choose a Resetting Method:
The inlet reset can be done two different ways:
1. Reset the minimum position only:
The inlet closes during the Reset Time Delay each time a reset is
performed. Once the inlet position is reset, the inlet returns to its
previous position. Set internal switch #8 to OFF to use this reset
method.
2. Reset toward the nearest position:
Each time a reset starts, the inlet panel is directed
towards the closest position from its current open-
ing: it then opens or closes during the Reset Time
Delay. Once the reset is completed, the inlet returns
to its previous position. This function prevents clos-
ing the air inlet when the room temperature already
asks for a large opening of the panel. Set internal
switch #8 to ON to use this reset method.
24
ITA-6 rev.02
This resetting method requires the pres-
ence of limit switches at both ends of
the actuator.
ON
OFF
ON
OFF