Comlink-2 Location & Connection
a. Unplug each unit.
b. Plug the communication card in the unit.
Open the cover. Drill a 5/16" hole through the bottom of the controller and
thread the communication cable through the hole. Use the grommet pro-
vided to secure the cable. Connect the cable to the terminals of the com-
munication card as shown below. When connecting two cable ends to-
gether, solder the joint and use a heat shrink to ensure a proper contact.
Line-up the comlink card with the con-
nector and insert it in the upright posi-
tion (see illustration beside). For com-
munication, always use a 1 twisted pair
shielded cable. The maximum length of
the cable is 10 000 ft (3 000 m) and
the recommended wire diameter is of
18 AWG (1.0 mm
tection module when running the cable
between buildings.
12
ITA-6 rev.02
). Use a lightning pro-
2
COMLINK-2 CARD