Download Print this page
Lutron Electronics PowPak RMJS-CCO1-24-B Installation

Lutron Electronics PowPak RMJS-CCO1-24-B Installation

Cco module

Advertisement

Available languages

Available languages

Quick Links

PowPak
| Installation
®
CCO Module
Part of the Energi TriPak
Family
®
24 V~ 45 mA
RMJS-CCO1-24-B
24 V- 35 mA
URMJS-CCO1-24B
UL 2043 Plenum Rated
*
For set-up, programming, and troubleshooting with a Vive
system, please refer to the installation instructions included
with the Vive
hub or at www.lutron.com
TM
Note for Replacement:
RMxS and URMxS - the "S" model can replace the non-"S" model
Important Notes:
Please read before installing.
• For installation by a qualified electrician in accordance with all local and national
electrical codes.
• Note: Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely before
installation.
• Operate between 32 °F (0 °C) and 131 °F (55 °C).
• 0% to 90% humidity, non-condensing.
• For indoor use only.
WARNING
Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
PowPak
®
CCO Module
Install in center of room to
maximize RF coverage.
Radio Powr Savr
TM
Occupancy Sensor
30 ft (9 m)
Maximum
Pico
®
Remote
Control
40 ft (12 m)
All Wireless Transmitters must be installed within
30 ft (9 m) of the PowPak
CCO Module.
®
FCC / IC Information:
This device complies with part 15 of the FCC Rules and Industry Canada licence-exempt RSS
standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and
(2) This device must accept any interference, including interference that may cause undesired operation.
Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user's authority to
operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
Required Components
For each system ensure you have:
At least one PowPak
CCO Module.
041505
®
Rev. A
09/2015
Load
NEC
CLASS 2
®
Status
LED
CCO Toggle
TM
Advanced
Operations
Contact
Closure
Output
(CCO)
(Class 2)
PowPak
CCO Module
®
Start Here
R
1
Install PowPak
Relay Module
R
When installing a PowPak
CCO Module,
use the supplied conduit nut and wire the module
as shown.
Suggested Installation Location:
Install in center of room.
This ensures proper RF coverage of area.
Note: PowPak
CCO Module may also be
®
mounted on or inside a junction box.
If installing unit inside a junction box please
see Application Note #423.
For more information:
www.lutron.com/powpakcco
2
Associate Wireless Transmitters to PowPak
Before beginning this step, make sure that there are no other PowPak
from other systems can be incorrectly associated to this system.
A
3
Permanently Install
Wireless Transmitters
Note: Please consult individual component
installation guides for information.
Link
Test
Need Help? www.lutron.com or call the Lutron Technical Support Center, at 1.800.523.9466
At least one Wireless Transmitter.
+
Link
Test
Radio Powr Savr
Radio Powr Savr
Occupancy
TM
Daylight Sensor
Sensor (10 maximum)
(1 maximum)
Supply Voltage
24 V~ / 24 V-
Wire nut
(2 Supplied)
COM
(Common)
NC
NO
(Normally Closed)
(Normally Open)
*
R
CCO Module
modules being set up within the same building. It is possible that Wireless Transmitters
®
B
Hold the CCO Toggle
Hold the indicated button on a Wireless Transmitter for
button on the PowPak
6 seconds to associate the device.*
®
CCO Module for 6 seconds
Repeat for any additional Wireless Transmitters.
to enter association mode.
* If no g button, hold "Lights Off" button.
Note: The CCO will open and
C
Hold the CCO Toggle button on the PowPak
close once after each step to
confirm successful completion.
CCO Module for 6 seconds to save association(s).
*
4
Daylight Sensor setup
Calibration
A
Turn lights in room on using the CCO
Toggle button on the PowPak
CCO
®
Module or an associated Pico
.
®
B
Press & hold "Cal." on the associated
Daylight Sensor for 6 seconds.
C
Exit room for 5 minutes to allow
calibration to be completed.
Note: When calibration has completed, all
lights will flash and the system will begin
daylighting.
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty
service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
Pico
Remote
This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase. This
®
Control
warranty does not cover the cost of installation, removal or reinstallation, or damage resulting from misuse, abuse, or damage from improper
wiring or installation. This warranty does not cover incidental or consequential damages.
(10 maximum)
LUTRON'S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE MANUFACTURE,
SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow the
exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above limitations
Cal.
may not apply to you.
Lutron, Energi TriPak, Pico, and PowPak are registered trademarks and Radio Powr Savr and Vive are trademarks of
TM
Lutron Electronics Co., Inc.
NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts.
©2015 Lutron Electronics Co., Inc.
Note: CCO Module supply wires can be
connected in any polarity.
Mounting screw
(2 Supplied)
To CCO-controlled device
Note: When wiring CCO output,
use 20 AWG to 16 AWG
(0.5 mm
2
to 1.5 mm
2
) solid or stranded wire.
Link
®
Tuning (Optional)
Link
Cal.
Test
A
If it is desired to have multiple zones of
lights turn on at different daylight levels
(using multiple CCO Modules with one
Daylight Sensor) follow the Tuning
procedure described in the Daylight Sensor
(LRF2-DCRB) installation instructions.
Use the CCO Toggle button in place of the
Dimmer/Switch tap button referenced in
the document.
CCO Information
• This product features a single contact closure output with both
normally open (NO) and normally closed (NC) dry contacts.
• The CCO incorporates maintained output behavior only.
• The CCO is rated to switch resistive loads at
Switching
Resistive
voltages up to 24 V only. To properly control
Voltage
Load
inductive load types such as relays, solenoids,
0-24 V-
1.0 A
or motors, refer to Application Note #434.
0-24 V~
0.5 A
Transmitting Device Transmitted Command
CCO Default Action
Pico
On
NO = Close, NC = Open
®
Remote Control
Off
NO = Open, NC = Close
Raise
No Action
Lower
No Action
Preset
NO = Close, NC = Open
Radio Powr Savr
Occupied
NO = Close, NC = Open
TM
Occupancy Sensor
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
Occupied
No Action
TM
Vacancy Sensor
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
Ambient light below target
NO = Close, NC = Open
TM
Daylight Sensor
level
Ambient light above target
NO = Open, NC = Close
level
Unaffected Mode
Unaffected Mode allows a system with an Occupancy Sensor
associated to multiple CCO Modules to be set up such that only
selected loads turn on automatically. Other loads will require a manual
turn-on with a Pico
Remote Control. All loads will turn off automatically
®
when the room is vacated.
A On a CCO Module, press and hold both the CCO Toggle and
Advanced Operations ("ADV") buttons for 6 seconds until the LED
begins flashing quickly.
B On the associated Occupancy Sensor, press and hold the "Test"
button* for 6 seconds until the lens flashes.
C Unaffected mode will be exited automatically. This CCO Module will
now be unaffected by occupancy commands. Repeat procedure
for any additional devices.
* If no "Test" button, hold "Lights On" button.
Test
Reset Factory Defaults
Note: In some instances it may be necessary to reset the PowPak
CCO Module back to factory default settings.
A Triple-tap the Advanced Operations ("ADV") button on the CCO
Module and hold until the LED begins to flash slowly.
B Within 3 seconds of flashing, release and triple-tap the button again
and the LED will flash rapidly indicating that the unit has been reset
to factory defaults.
Note: Any associations or programming previously set up with the
unit will be lost and will need to be re-programmed.
Troubleshooting *
www.lutron.com
CCO-
• Ensure breaker to the PowPak
CCO Module is on.
®
controlled
• Ensure the CCO-controlled device has been
device does
properly wired to the PowPak
CCO Module.
®
not respond
• Ensure Wireless Transmitter is properly associated
to Wireless
to PowPak
CCO Module.
®
Transmitter(s)
• Ensure Wireless Transmitter's battery is installed
correctly.
Wireless
• The maximum number of Wireless Transmitters
Transmitter(s)
have been associated to the PowPak
CCO
®
cannot be
Module. To remove a previously set up Wireless
associated to
Transmitter, tap the button used for association on
PowPak
CCO
the Wireless Transmitter three times, on the third
®
Module
tap hold for three seconds and then tap three more
times.
R
®

Advertisement

loading

Summary of Contents for Lutron Electronics PowPak RMJS-CCO1-24-B

  • Page 1 Note: Any associations or programming previously set up with the Permanently Install Daylight Sensor setup unit will be lost and will need to be re-programmed. Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s authority to operate this equipment. Wireless Transmitters Calibration...
  • Page 2 Lutron, Energi TriPak, Pico, et PowPak sont des marques déposées et Radio Powr Savr et Vive sont des marques de commerce de Remarques importantes : Lutron Electronics Co., Inc. NEC est une marque déposée de la National Fire Protection Association, Quincy, Massachusetts. Module CCO PowPak...
  • Page 3 Sensor de presencia Radio Powr Savr Notas importantes: Lea antes de la instalación. Lutron Electronics Co., Inc. NEC es una marca registrada de National Fire Protection Association, Quincy, Massachusetts. Módulo PowPak Radio Powr Savr (Máximo de 10) (Máximo de 1) ®...
  • Page 4 (CCO) Sensor de luz natural Lutron, Energi TriPak, Pico, e PowPak são marcas registradas e Radio Powr Savr e Vive são marcas comerciais da Lutron Electronics Co., (Classe 2) Sensor de ocupação Notas importantes: Por favor leia antes de instalar.

This manual is also suitable for: