Toshiba MMF-UP0151H-E Installation Manual page 26

Table of Contents

Advertisement

Check code
Outdoor unit 7-segment display
Wired remote
controller display
01: Comp. 1 side
P26
P26
02: Comp. 2 side
03: Comp. 3 side
01: Comp. 1 side
P29
P29
02: Comp. 2 side
03: Comp. 3 side
P31
*1 Inverter quantity information
(Super Modular Multi System i series (SMMS-i))
Comp. Inverter
Fan
No.
Inverter
1
2
3
01
Comp. 1
02
Comp. 2
03
Comp. 1 + Comp. 2
04
Comp. 3
05
Comp. 1 + Comp. 3
06
Comp. 2 + Comp. 3
07
Comp. 1 + Comp. 2 + Comp. 3
08
Fan
09
Comp. 1 + Fan
0A
Comp. 2 + Fan
0B
Comp. 1 + Comp. 2 + Fan
0C
Comp. 3 + Fan
0D
Comp. 1 + Comp. 3 + Fan
0E
Comp. 2 + Comp. 3 + Fan
0F
All
: Inverter trouble
Trouble detected by central control device
Check code
Outdoor unit 7-segment display
Central control
device indication
C05
C06
C12
P30
(L20)
49-EN
Auxiliary code
Operation
*1 Inverter quantity information
(Super Modular Multi System e and u series (SMMS-e, SMMS-u))
Trouble
No.
01
02
03
08
09
0A
0B
10
11
12
13
18
19
1A
1B
Wireless remote controller
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Differs according to trouble contents of unit with occurrence of alarm
– 25 –
Wireless remote controller
Sensor block display of receiving unit
Timer
Ready
Flash
ALT
ALT
ALT
Fan
Comp. Inverter
Inverter
1
2
1
2
Comp. 1
Comp. 2
Comp. 1 + Comp. 2
Fan1
Comp. 1 + Fan1
Comp. 2 + Fan1
Comp. 1 + Comp. 2 + Fan1
Fan2
Comp. 1 + Fan2
Comp. 2 + Fan2
Comp. 1 + Comp. 2 + Fan2
Fan1 + Fan2
Comp. 1 + Fan1 + Fan2
Comp. 2 + Fan1 + Fan2
All
: Inverter trouble
Ready
Flash
Sending trouble in central control device
Receiving trouble in central control device
Batch alarm of general-purpose equipment control interface
Group control follower unit trouble
• Duplication addresses of indoor units in central control device
(L20 is displayed.)
• With the combination of air conditioning system, the indoor unit may detect the check code
of L20
Check code name
IPM short protection trouble
Comp. position detective circuit system trouble
Other indoor unit trouble
(Group follower indoor unit trouble)
• For details about check codes determined with an Interface
P.C board or an Inverter P.C board, refer to the Installation
Manual of the outdoor unit.
Trouble
Check code name
Judging device
Compressor inverter
Compressor inverter
Indoor unit
Judging device
Central control device
Central control device
General-purpose
equipment I/F
Central control device
50-EN