 Connecting drain pipe
Drain pan
REQUIREMENT
• Using adhesive agent for vinyl chloride, connect the hard vinyl chloride pipes certainly so that water does not leak.
• It requires several hours to dry and harden the adhesive agent.
(Refer to Guide Manual of the adhesive agent.)
In this time, do not apply force to the connecting section with the drain pipes.
Piping method
Drain and refrigerant pipes can be drew out from left, right, back or bottom depending on the installation location.
However, drain pipes can be drew out from left only when the refrigerant pipes are drew out from left. The drain
hose must be fix to the refrigerant pipe with binding band and installed with gradient of 1/100 or more. The drain
hose end connected to the indoor unit must be free from external force.
• Do not route the drain hose and refrigerant pipes over the electrical control box. Condensed water from the pipes
may enter the electrical control box and cause malfunction. Exclude UP015 to UP027 models.
• On the UP015 to UP027 models, the drain hose and refrigerant pipes coming out of the electrical control box
must be 5 mm apart. If the clearance is less than 5 mm, it will be hard to remove the drip-proof cover and the
electrical control box cannot be taken out.
Piping port at bottom
23-EN
Heat insulator
Hard polyvinyl chloride pipe
Drain hose
Adhesion for hard polyvinyl
chloride pipe used
Refrigerant pipe connecting
port (both sides)
Wiring port
(both sides)
Drain hose connecting port
(both sides)
*UP036 to UP056 only
To connect drain hose on
right or left , route it through
the knock-out for refrigerant
Piping port at
piping on UP015 to UP027
back
model.
• To connect drain hose on left
Refrigerant
Drain pan
piping
PVC pipe
(Drain piping)
Drain hose
Heat
Fix with binding band.
insulator
Fix the drain hose to the refrigerant pipe
with binding bands without hanging down
and slack. fix 3 points
Do not bind the drain hose and refrigerant
pipe (heat insulator) too tight.
*Connect and fix drain pipe at outside of the unit on site.
Install the drain hose with gradient of 1/100 or more to
connect it to unit on both left and right sides.
 Check the draining
• After piping work has been completed, remove the air intake grille and pour water in the drain pan to check water
drain and that there is no water leakage from connecting part of the drain hose.
• After check of the water drain, attach the air intake grille as before.
– 12 –
• To connect drain hose on right
Drain pan
PVC pipe
(Drain piping)
Drain hose
Heat insulator