Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers.
Incorrect connection causes a trouble.
• Pass the wires through the bushing of wiring holes of
the indoor unit.
• The low-voltage circuit is provided for the remote
controller. (Do not connect the high-voltage circuit)
<How to remove the electrical control box cover>
• UP015 to UP027 models
Take off screws (1) and (2) at this side of the
electrical control box and remove the drip-proof
cover.
Take off screws (3) and (4) at front side of the
electrical control box and remove the electrical
control box cover.
• UP036 to UP056 models
Take off screws (3) and (4) at front side of the
electrical control box and remove the cover of the
electrical control box.
(The drip-proof cover is provided to UP015 to UP027
models only.)
<Wiring>
• Draw the wire into the wiring hole (knockout hole).
• Attach a supplied rubber bush to the wiring hole
(knockout hole).
• Be sure to fix the connecting wires using two cord
clamps as shown in the figure. Do not apply tension
on the connecting part of the terminal block.
• Be sure to mount cover of the electrical control box
and the drip-proof cover.
Drip-proof cover
(UP015 to UP027
(1)
only)
(2)
Electrical control
box cover
(3)
(4)
Electrical control box
33-EN
<Positioning of hole for wiring (Knock-out hole) >
UP036 to UP056
UP015 to UP027
Wiring hole (Knock-out hole)
Wiring hole (Knock-out hole)
Indoor / Outdoor control
wire / Remote controller
terminal block
Power supply
Uv(U1) Uv(U2) A B
terminal block
L
N
U
U
A B
1
2
R(L) S(N)
R
S
Power supply wiring
Earth screw
Cord clamp*
* Match the cord clamp length with size of connecting wires by
positioning holes on the clamp to hold the wire and fix the cord
clamp with screw.
* Be sure to fix the connecting wires using two cord clamps as
shown in the figure.
R
S
(L)
(N)
Indoor / Outdoor connecting wire
See the figure on the above
Earth line
for connecting wires to the
Power
terminal block.
supply wire
– 17 –
Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
Terminal block for remote
controller wiring of indoor unit
Address setup
Set up the addresses as per the Installation Manual supplied with the outdoor unit.
Remote controller wire
Terminal block
(Locally procured)
A
A
Remote controller unit
B
B
34-EN